Installation
ONEAC Sinergy SE II Series UPS User Manual
13
Output Terminal
Voltage
ATTENTION: *X2 & X3 are wired together, and X5 and X6 are wired together to provide full nameplate
rated current at 120 V (50 A for 6 kVA model and 83 A for 10 kVA model). However, each terminal can supply
only 1/2 of the total current and both terminals MUST be connected to the load in order to provide full power.
ATTENTION: *X2 provides only 1/2 of nameplate rated current power (25 A for 6 kVA model and 40 A
for 10kVA model. User must provide over current protection (fuse or circuit breaker) of proper size
.
ATTENTION: *X2 & X3 are wired together, and X5 and X6 are wired together to provide full nameplate
rated current at 100 V (50 A for 6 kVA model and 83 A for 10 kVA model). However, each terminal can supply
only 1/2 of the total current and both terminals MUST be connected to the load in order to provide full power.
Table 5. 120/208/240 Output Terminal Voltage Configurations
X1
X2
X3
E/G
X4
X5
X6
Terminal Voltage
(-)120
0
0
-
88
(+)120* (+)120*
120 Volts (from X2 and X3
to X5 and X6)
208 Volts (from X1 to X4)
240 Volts (from X1 to X6)
Table 6. 120/208/230/240 Output Terminal Voltage Configurations
X1
X2
X3
E/G
X4
X5
X6
Terminal Voltage
0
120*
-
-
208
230
240
Table 7. 100/200 Output Terminal Voltage Configurations
X1
X2
X3
E/G
X4
X5
X6
Terminal Voltage
(-)100
0
0
-
-
(+)100* (+)100*
100 Volts (from X2 and X3
to X5 and X6)
200 Volts (from X1 to X6)