Chapter 3 Installation
9
Chapter 3 Installation
3.1 Basic requirements
The protection level of CPS SC500KTL, CPS
SC250KTL-H photovoltaic inverter is IP20. Please DON’T
install the equipment in a humid environment.
9
Check and make sure that the ambient temperature
of the installation environment is
-
25
°
C
~+
60
°
C;
9
Make sure that the public power grid voltage is
215
~
310Vac (Default value is 243~297Vac and the
parameter can be adjusted on the LCD display panel
according to the actual grid voltage.) and the grid
frequency is 50Hz;
9
Permission of grid connection has been granted by
the local electric power authority;
9
Installation personnel must be qualified electricians
or people who have received professional training;
9
Sufficient convection space;
9
Away from flammable and explosive substances
3.2 Mechanical installation
(1) Dimensions
Dimensions of CPS SC500KTL grid-tie PV inverter are
shown in Figure 3-1.