Chapter 3 Installation
18
Figure 3-10 Sketch of external wiring
3.3.1 DC connection
(1) The following rules should be abided by to ensure
the highest efficiency of the PV inverter:
(a) First, make sure that the maximum open circuit
voltage of the PV modules is lower than 1000Vdc
for CPS SC500KTL-H and CPS SC250KTL-H
under any conditions; For CPS SC500KTL, the
maximum open circuit voltage of the PV modules
should be lower than 880V.
(b) Ensure that the polarity of DC input is correct, i.e.
the positive pole of PV module is connected to the
All the external cables should be
routed from the conduit holes at the
bottom.