Chapter 3 Installation
19
positive pole of the inverter’s DC input, and the
negative pole of PV module is connected to the
negative pole of the inverter’s DC input;
(c) The Max. DC input current of the inverter is 600A,
so 35
~
120mm
2
copper core cables are
recommended for inverter’s DC input, as shown in
Table 3-2
:
Table 3-2
8 strings
5 strings
4 strings
3 strings
Positive
35mm²
50 mm²
70 mm²
95~120 mm²
Negative
35mm²
50 mm²
70 mm²
95~120 mm²
Bolts M8
(2) Confirm that the input PV modules are of the same
specifications and types before connection of DC input;
(3) Connect the positive and negative terminals of DC
cables to the corresponding inverter’s copper bar terminals
of DC side, as shown in Figure 3-11.
Figure 3-11 Sketch of external wiring
Positive Pole
Negative Pole