Chapter 3 Installation
26
(1) No. 1 and 2 connectors of Terminal can be used
①
to connect 220V AC power supply as the operating power of
inverter. If outside power is selected as the operating power
of inverter, the AUX POWER SELECTION switch at the
upper place should be turned to “OUTSIDE”. If the internal
grid-tie power is used as the operating power, AUX POWER
SELECTION switch should be turned to “INSIDE”.
(2) No. 1 and 2 connectors of Terminal
②
can be used
to connect dry contacts as the input of inverter control.
(3) No. 1 and 2 connectors of Terminal
③
can be used
as the fault alarm contacts of inverter.
Note: For CPS SC500KTL, outside power is available to
be used as the operating power for both of the DC input
cabinets or each of them. The internal grid-tie power is also
available to be used as the operating power for both of the
DC input cabinets or each of them.