36
Chapter 4 Operation
operation after another one according to the intensity of
sunlight. It will disconnect from the power grid when the
sunlight is very weak. The inverter will try to connect to the
grid and generate power again when the photovoltaic array
voltage is stable and higher than 470V.
4.4 Fault shutdown
When the photovoltaic power generation system of CPS
SC500KTL fails, such as output short circuit, grid
overvoltage/undervoltage, grid overfrequency/underfrency,
high ambient temperature or internal failure of the machine,
one 250KW cabinet or maybe two of them will stop working
completely.
When the photovoltaic power generation system of CPS
SC250KTL-H fails, the inverter will stop working instantly. At
this moment, if the DC circuit breaker is NOT turned off and
the system can take POWER ON/OFF movements
automatically, it is detected that there is NO permanent fault
in the system.
If the inverter breaks down, the faults can not be
eliminated until the system is reset. If service personnel
need to maintain the inverter, please refer to the part of
“Manual Shut-down for maintenance”.
When DC overvoltage, overcurrent, reverse polarity
connection of DC input or interruption of 3 phase AC output
(if inside power supply is selected), or interruption of 220V
AC (if outside power supply is selected), the system will turn