Chapter 4 Operation
39
Warn/Protect/
Fault
Definition Possible
causes
Recommended
solutions
5
、
Warn004x Inside
warning
Lightning surge
protector on DC side
has an open circuit
1
、
Observe for 5
minutes and see
whether the alarm will
be eliminated
automatically;
2
、
Contact after-sales
service personnel
6
、
Warn005x Inside
warning
Temperature sensor
detects that the
temperature inside
inverter exceeds
normal range
1
、
Observe for 5
minutes and see
whether the alarm will
be eliminated
automatically;
2
、
Contact after-sales
service personnel
7
、
Warn006x Inside
warning
It is detected that the
average AC output in
Cabinet 1/2 is 30A
larger than that in
Cabinet 2/1
1
、
Observe for 5
minutes and see
whether the alarm will
be eliminated
automatically;
2
、
Contact after-sales
service personnel
8
、
Warn007x Inside
warning
Lightning surge
protector on AC side
has an open circuit
1
、
Observe for 5
minutes and see
whether the alarm will
be eliminated
automatically;
2
、
Contact after-sales
service personnel