Chapter 1 IMPORTANT SAFETY INSTRUCTIONS
2
command is carried out successfully through LCD button
operations.
2. This inverter is specially designed to connect AC power to
the public grid. Do not connect the AC output of this
equipment directly to private AC power equipments.
3. If the DC circuit breaker is tripped because of malfunction,
it is prohibited to turn on the DC circuit breaker directly.
System reset program must be executed and then turn on
the DC circuit breaker according to the indication on the
LCD.
4. Before opening the inverter for maintenance, shut down
the inverter through LCD operation. Turn off the DC circuit
breaker, execute the De-energy program and then turn off
the AC circuit breaker. The inverter should not be maintained
until the voltmeter shows that there is no electric charge left
in the DC bus capacitor
!
CAUTION:
1. Pay attention to inverters’ center of gravity and
recommend users to use forklifts to carry.
2. The command of De-energy will be ineffective if the
inverter is being energized. Wait and execute the command
until the process of De-energy is completed.
3. If software needs to be updated, AC and DC circuit
breakers must be turned off and the auxiliary power mode