54
Chapter 5 Human Machine Interface
5.3.7 System protection parameter setup
By pressing PAGEDOWN and ENTER at the same time
in the main interface and entering the password
(PAGEUP->PAGEDOWN->RIGHT->LEFT), the system
parameter setup menu is entered, as shown in Figure 5-11.
This menu includes 4 submenus: “1 SysPara”, “2 Restart”, “3
Recover” and “4 ClrErrRecd”.
(1) Set up the system protection parameters in “1
SysPara” menu. The types of protection parameters are
shown in Table 5-3.
(2) “2 Restart” menu. If an internal fault shutdown
happens, a severe fault has occurred inside the inverter. The
user may perform a force restart once in this menu if the user
needs to restart the inverter. Note that this function is
effective only when a fault shutdown occurs. The inverter
may restore to normal operation automatically if alarm or
protection faults occur. This function will not respond when
the inverter is in operation mode and a “FaultOperated”
alarm interface will pop up.
(3) “3 Recover” menu, the manufacturer’s parameter
default value can be restored when the inverter is not in
operation mode. Otherwise, a “FaultOperated” will be
prompted.
(4) In “4 ClrErrRecd” menu, history information of the
faults can be cleared. A confirmation is required to clear the
records.