56
Chapter 5 Human Machine Interface
Table 5-3 Protection Parameters Table
No.
Description of
parameter
LCD indication
Setup range (lower limit,
default & upper limit)
1
Grid voltage
upper limit (V)
GridV.Max(V)
(
200.0,297.0,365.0V
)
2
Grid votage
lower limit (V)
GridV.Min(V)
(
0,243.0,270.0V
)
3
Grid frequency
upper limit (Hz)
GridF.Max(Hz) (50.00,50.50,65.00Hz)
4
Grid frequency
lower limit (Hz)
GridF.Min(Hz) (45.00,49.50,60.00Hz)
5
Isolation
resistance lower
limit (KOhm)
IsoResis(KOhm)
(1.0,10.0,500.0K
Ω
)
6
Active power
derating (%)
PowerDerating
(%)
(
10.0%,100.0%,100.0%
)
7
Reactive
Compensation
(%)
ReactiveComp
(%)
(
-0.900,1.000,0.900
)
8
PV start voltage
(V)
PVStartVol(V)
(
430.0,470.0,600.0V
)