22
Before performing any electrical connections, ensure that both DC
and AC Switches are OFF. Otherwise, fatal injury can occur due to
the high voltage caused from AC and DC cables.
CAUTION
DANGER
Grounding the PV Strings needs below prerequisites:
An isolation transformer must be installed on the AC side of each inverter;
Ensure that the neutral wire of the isolation transformer must be disconnected from the
PGND cable.
One isolation transformer is with one PV inverter: do not install a single isolation transformer
for multiple inverters; otherwise, circulating current generated by the inverters will lead to
operation failure.
Select Isolation setting on the APP
ChintHome
, and set in Input Grounded, With TF.
The ground cable and OT terminals have been prepared.
a. Ground cable: Outdoor copper-core cables with a cross sectional area of 4 mm or more are
recommended.
b. OT terminal: OT6~4.
5.1.1 Preparation
Key parameter
Product series code
Terminal product series code
NOTE
Good grounding for the inverter helps resist the impact of surge
voltage and improve the EMI performance. Connect the PGND cable
before connecting the AC power cables, DC power cables, and
communications cables.
OT 6
~
4
2
5 Electrical Connections
5.1 Connecting Protection Ground (PGND) Cables
CPS SCA-S/
SM Series Inverter