135
Backup heater
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
46
00
B ackup heater type of function
0=disable
1=Replacement mode
2=Emergency mode
3=Supplementary mode
0
0
3
-
Par4600 and Par4700
are synchronized
Par4600=1, 2, 3
→Par4700=0
Par470=1, 2
→Par4600=0
I
46
01
Manual water set point
50.0
40.0
60.0
0.5°C
I
46
02
Manual water temperature hysteresis
5.0
0.5
10.0
0.5°C
I
46
04
Heater activation delay time
5
0
900
1min
I
46
05
Integration time for starting heaters
600
0
900
°C×sec
(Outgoing water
temperature
– Actual temperature)
x Integration time
calculate every 1sec.
I
46
10
C onditions to be available Backup heaters
0=always enabled
1=depends on Outdoor air temperature
1
0
1
-
I
46
11
Outdoor air temperature to enable Backup heaters
and disable compressor
-5.0
-20.0
20.0
0.5°C
I
46
12
Outdoor air temperature hysteresis to disable Backup
heaters and enable compressor
5.0
0.5
10.0
0.5°C
I
46
13
Outdoor air temperature to enable Backup heaters
(Supplementary mode)
5.0
-20.0
20.0
0.5°C
I
46
14
Outdoor air temperature hysteresis to disable Backup
heaters (Supplementary mode)
5.0
0.5
10.0
0.5°C
I
46
20
F reeze protection functions
0=disable
1=enabled during Start-up
2=enabled during Defrost
3=enabled during Start-up and Defrost
0
0
3
-
I
46
21
Outgoing water temperature set point during Start-up
8.0
0.0
60.0
0.5°C
I
46
22
Hysteresis water temperature set point during Start-up
5.0
0.5
10.0
0.5°C
I
46
23
Outgoing water temperature set point during Defrost
24.0
10.0
50.0
0.5°C
I
46
24
Hysteresis water temperature set point during Defrost
5.0
0.5
10.0
0.5°C
EHS (External heat source)
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
47
00
E HS type of function
0=disable
1=Replacement mode
2=Supplementary mode
0
0
2
-
Par4600 and Par4700
are synchronized
Par4600=1, 2, 3
→Par4700=0
Par470=1, 2
→Par4600=0
I
47
01
C onditions to be available EHS
0=always enabled
1=depends on Outdoor air temperature
1
0
1
-
I
47
02
Outdoor air temperature to enable EHS and disable
compressor
-5.0
-20.0
20.0
0.5°C
I
47
03
Outdoor air temperature hysteresis to disable EHS
and enable compressor
5.0
0.5
10.0
0.5°C
I
47
04
Outdoor air temperature to enable EHS
(Supplementary mode)
5.0
-20.0
20.0
0.5°C
I
47
05
Outdoor air temperature hysteresis to disable EHS
(Supplementary mode)
5.0
0.5
10.0
0.5°C
I
47
06
EHS activation delay time
5
0
900
1min
I
47
07
Integration time for starting EHS
600
0
900
°C×sec
(Outgoing water
temperature
– Actual temperature)
x Integration time
Calculate every 1 sec
9. Parameters List
Summary of Contents for AEYC-0639U-CH
Page 156: ...20810030 M ...