140
11. Service and Maintenance
In the event that an error is detected, the error code will be displayed in Remote controller and PCB (Terminal) display.
As for the display in Remote controller, LED (red) on ON/OFF switch will be flashed, and warning icon and 2 or
3digits error code will be displayed on LCD screen. Error code (2digits) will be displayed on the PCB (Terminal)
display.
11.1 Error code display
11.2 Error history display
・
The previous 10 error codes can be displayed on PCB (Terminal) display.
Procedure to display on PCB(Terminal) display
・
Press Pump SW and Reset SW on PCB (Terminal) at the same time for 5 seconds, error history order and error
code will be displayed alternately. The first one is the latest error code.
・
Press Pump SW to go up the history order and it is up to 10th error code then go back to the latest error code.
・
When there is no error history, “--” will be displayed.
If no operation is carried out for 5 minutes, or the same procedure is operated to display error history, the display
returns to normal display.
Deletion of the error history
・
During error code displaying, press Reset SW for 10 seconds to delete the error history.
PCB(Terminal)
Reset SW.
Pump SW.
Display
warning icon
and error code
Remote controller
LED(red)
PCB(Terminal)
Reset SW.
Pump SW.