7.2.1 Fixed set point
The heat pump will operate based on the fixed outgoing water set-point defined by parameters.
The installer will set the value for Heating and Cooling, defined per each Zone by dedicated parameter.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
21
00
H eating Zone1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve
0
0
1
-
I
21
01
Heating Zone1, Fixed Outgoing water set point in Heating
45.0
23.0
60.0
0.5°C
I
21
10
H eating Zone2, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
11
Heating Zone 2, Fixed Outgoing water set point in Heating
45.0
23.0
60.0
0.5°C
I
21
20
C ooling Zone 1, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
21
Cooling Zone 1, Fixed Outgoing water set point in Cooling
7.0
7.0
23.0
0.5°C
I
21
30
C ooling Zone2, enable Outgoing water set point
0=Fixed set point
1=Climatic curve enabled
0
0
1
-
I
21
31
Cooling Zone2, Fixed Outgoing water set point in Cooling
7.0
7.0
23.0
0.5°C
I
21
41
Hysteresis of water set point in Heating and DHW
8.0
0.5
10.0
0.5°C
I
21
42
Hysteresis of water set point in Cooling
8.0
0.5
10.0
0.5°C
7.2 Water temperature set point
The water temperature set point can be selected with “traditional” mode, i.e. based on a fixed set point
programmed by the user, or in “advanced” mode, with a variable set point calculated automatically using climatic
curves, both in Heating and Cooling mode, as described below. The choice between Fixed set point or variable set
point will be defined by dedicated parameter.