7.5.7.2 Additional water pump2
A parameter can be used to set the desired type of pump operation, as follows:
Depending on Main water pump setting
Depending on Main water pump setting but always OFF when the DHW mode is activated
Always ON, apart from if any alarms are active or if the HP unit is in OFF mode
ON/OFF based on Room air temperature (set by Remote controller)
Note: As for above sentence No. , “OFF mode” means Power supply for HP unit is ON, and with no operation
for Heating/Cooling/DHW.
Additional water pump2
230V 50Hz
P
PCB(Terminal)
Dehumidifier
Neutral
EHS
45
46
47
48
49
N
41
42
43
44
Electric
heater
Heating
Cooling
mode
output
Alarm
Pump1
Pump2
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
51
49
T erminal 49 :Pump2
0=disable
1=2nd Additional water pump2 for Zone2
0
0
1
-
I
42
20
T ype of operation of additional water pump
0=disable
1=depending on Main water pump setting
2= depending on Main water pump setting but always
OFF when the DHW mode is activated
3= always ON, apart if any alarms are activated or if
the HP unit is in OFF mode
4=ON/OFF based on Room air temperature
0
0
4
-
82
7. Unit Management