7.5.13 Space Heating management
The System controller recognizes 3 zones (Zone1, Zone2, and DHW tank)
The System controller uses the “zone of greatest demand” strategy for calculating the Outgoing water temperature
required from the HP unit (and/or EHS as Electric heater or Boiler).
Zone1: The mixed or direct Heating loop controlled by the Master Remote controller. Using the Master Remote
controller, it is possible to turn the HP unit ON/OFF, toggle between Heating and Cooling, set the Room air
temperature, set the Room humidity, and set the Time band for Zone1 and Zone2.
Zone2: The direct Heating loop controlled by the Slave Remote controller. Using the Slave Remote controller, it is
possible to turn the HP unit ON/OFF, and set the Room air temperature.
* The time and date setting and time band setting are carried out using the Master Remote controller.
DHW tank: The DHW tank loading loop (cylinder coil). The Master Remote controller is used to specify the DHW
related settings.
Each Zone can generate a demand to the HP unit (and/or EHS as Electric heater or Boiler) for a particular supply
water temperature
Zone1: The Outgoing water set point required by the “Zone1” Heating loop or Cooling loop
Zone2: The Outgoing water set point required by the “Zone2” Heating loop or Cooling loop
DHW tank: The Outgoing water set point required by the DHW loop.
Buffer tank
3way valve
EHS
DHW tank
Zone1
Zone2
Master
Remote controller
M
Mixing
valve
M
Pump1
Pump2
Salve
Remote controller
HP unit