10
GENERAL NOTES for configuration.
FUNC =
This will memorize the new value of
the selected parameter and go to the
next parameter (increasing order).
MAN =
This will scroll back the parameters
without memorization of the new value.
s
=
This will increase the value of the
selected parameter
t
=
This will decrease the value of the
selected parameter.
CONFIGURATION PROCEDURE
1) Remove the instrument from its case.
2) Set the dip switch V101to the open condition
(see fig. 13).
3) Re-insert the instrument.
4) Switch on the instrument.
The display will show COnF.
NOTE
: If "CAL" indication is displayed, press
immediately the
s
pushbutton and return to
the configuration procedure.
5) Push the FUNC pushbutton.
SEr1 = Serial interface protocol
OFF
= No serial interface
Ero
= Polling/selecting ERO
nbUS = Modbus
jbUS
= Jbus
SEr2 = Serial link device address
Not available when SEr1 = OFF
From 1 to 95 for ERO protocol.
From 1 to 255 for all the other protocols.
NOTE
: the electrical characteristic of the RS 485
serial interface allows you the connection of 31
devices maximum.
SEr3 = Baude rate for serial link
Not available when SEr1 = OFF
From 600 to 19200 baud.
NOTE
: 19200 baud is shown on display as 19.2.
SEr4 = Byte format for serial link
Not available when SEr1 = OFF
7E = 7 bits + even parity (For ERO protocol only)
7O = 7 bits + odd parity (For ERO protocol only)
8E = 8 bits + even parity
8O = 8 bits + odd parity
8
= 8 bits no parity
P1 - Input type and standard range
0
= TC type
L
range
0 / +400.0 °C
1
= TC type
L
range
0 /
+900 °C
2
= TC type
J
range-100.0 / +400.0 °C
3
= TC type
J
range -100 / +1000 °C
4
= TC type
K
range-100.0 / +400.0 °C
5
= TC type
K
range -100 / +1370 °C
6
= TC Type T
range-199.9 / +400.0 °C
7
= TC type
N
range -100 / +1400 °C
8
= TC type
R
range
0 / +1760 °C
9
= TC type
S
range
0 / +1760 °C
10 = RTD type Pt 100 range-199.9 / +400.0 °C
11 = RTD type Pt 100 range -200 /
+800 °C
12 = mV
Linear range
0 /
60 mV
13 = mV
Linear range
12 /
60 mV
14 = mA
Linear range
0 /
20 mA
15 = mA
Linear range
4 /
20 mA
16 = V
Linear range
0 /
5 V
17 = V
Linear range
1 /
5 V
18 = V
Linear range
0 /
10 V
19 = V
Linear range
2 /
10 V
20 = TC type
L
range
0 / +1650 °F
1604-7-1-AB.p65
5/16/00, 10:50 AM
10