16
2 = the instrument starts in the same way it was
left prior to power shut down but if the
instrument was in manual mode, it will restart
with a power output equal to 0.
3 = the instrument starts in the same way it was
left prior to power shut down but if the
instrument was in manual mode, it will restart
with the same power output it had prior to
power shut down.
P36 = Timeout selection
This parameter allows to set the time duration of
the timeout for parameter setting used by the
instrument during the operating mode.
tn. 10 = 10 seconds
tn. 30 = 30 seconds
P37 = Conditions for output safety value
This parameter is skipped when none of the
outputs is programmed as control output.
0 = No safety value (see "Error Messages")
1 = Safety value is applied when overrange or
underrange condition is detected.
2 = Safety value is applied when overrange
condition is detected.
3 = Safety value is applied when underrange
condition is detected.
P38 = Output safety value
This parameter is skipped when none of the
outputs is programmed as control output or
P37 = 0.
This value can be set
- from 0.0 to 100.0 % when the device is
configured with one control output only.
- from -100.0 % to 100.0 % when the device is
configured with two control outputs.
P31 = Maximum value of the proportional band
calculated by the SMART algorithm.
This parameter is skipped when none of the
outputs is programmed as control output or
P30=0.
This parameter is programmable from P32 value
to 200.0 %.
P32 = Minimum value of the proportional band
calculated by the SMART algorithm.
This parameter is skipped when none of the outputs
is programmed as control output or P30=0.
It is programmable from 1.0% to P31 value.
P33 = Minimum value of the integral time
calculated by the SMART algorithm.
This parameter is skipped when none of the
outputs is programmed as control output or
P30=0.
It is programmable from 00.01[mm.ss] to 02.00
[mm.ss].
P34 = MANUAL function
This parameter is skipped when none of the
outputs is programmed as control output.
OFF = manual function is disabled
On =
manual function can be enabled/
disabled by MAN pushbutton.
P35 = Device status at instrument start up.
This parameter is skipped when none of the outputs
is programmed as control output or P34=OFF.
0 = the instrument starts in AUTO mode.
1 = the instrument starts in MANUAL mode with
power output set to 0.
1604-7-1-AB.p65
5/16/00, 10:50 AM
16