background image

5

3. Product Description                                                                                                                      

3.3.2 Operation Procedure of External Battery for Long Backup Time UPS

The battery connection procedure is very important for long backup model. Any incompliance may result in 

the risk of electric shock. Therefore, the following steps must be strictly complied with.

 

  1. First connect in series the batteries of the pack  

    to ensure proper battery voltage that 1K/1KL for 

 

    36VDC,  2K/2KL  for  72VDC  (or  96VDC), 

 

    3K/3KL for 96VDC.

  2. Take out the battery cable delivered with the  

    UPS, one end of the external battery cable is a 

 

    plug for connecting the UPS, the other end has 3 

 

    open wires for connecting the battery pack.

  3. Connect the external battery cable to the battery 

 

    terminal (DO NOT connect the battery socket of 

 

    the UPS first. Otherwise, it may cause electric 

 

    shock). Connect the red wire to the “+” 

 

    terminal of the battery. The black wire is 

 

    connected  to  the  “-”  terminal  of  the  battery. 

 

    The green/yellow wire is grounded for protection

 

  purpose.

  4. Connect  the  plug  of  the  external  battery  cable  to  the  external  battery  slot  on  the  rear  panel  of  the 

 

    UPS to complete the connection procedure.

  Note: The length of the external battery cable is 1.6 m, If users need a longer one, please consult the 

 

distributor. There is a limit to the length of the external battery cable to ensure normal operation of the UPS.

3.3.3 Connecting Communication Cable

1. Computer interface 

Computer interface: The type of signals is provided 

by the UPS to communicate with a host computer 

through  communication  cable  included  in  the 

 

standard accessory, User can use special monitor  

software UPSilon in the standard accessory to monitor 

the UPS through the port.

2. Alternative connection of communication

Intelligent Slot: It is designed for installing the dry 

contact  card,  SNMP  card  and  485  card.  You  can 

choose for one of them to installed.

a- dry contact card: You can utilize monitor function 

of dry contact to manage the power supply directly.

b- SNMP: It enables you monitor the UPS remotely 

through Internet.

c- 485: Central monitor card.

Note: Please remove the cover board of the intelligent 

slot before any card is installed.

•  Figure  3-3  Battery  connection  diagram  for 

Long Backup time models

BATTERY BANK

UPS

• Computer communication cable

RS-232

RS-232

• SNMP Card Slot

SNMP Card

Summary of Contents for Venus Smart 1K

Page 1: ...HUPHOTIC CO LTD ENERGY WAVE CO LTD CHUPHOTIC ELECTRONICS CO LTD 949 Moo 9 Sumrong Nue Muang Samutprakarn Samutprakarn 10270 Tel 02 186 3011 Fax 02 186 3018 19 Website www chuphotic com E mail ups chup...

Page 2: ...g Inspection 4 3 2 Installation Notes 4 3 3 Cable Connection 4 5 4 Operation LCD model 6 10 4 1 Operation Display Panel 6 4 2 Operation Mode 6 8 4 3 Operating Instructions 9 10 5 Maintenance 10 11 5 1...

Page 3: ...Do not short the positive and negative electrodes of battery Otherwise it may cause electric shock or fire 6 Do not plunge or insert any objects into the air vents and other inlets 7 Do not store or...

Page 4: ...el Remark 1K With a 1A internal charger and 3 build in batteries of 12V 7AH 2K With a 1A internal charger and 6 or 8 build in batteries of 12V 7AH 3K With a 1A internal charger and 8 build in batterie...

Page 5: ...battery through the DC DC converter 5 Bypass It is very important in the UPS system In the event of a UPS fault that will not lead to UPS shutdown the load will be automatically transferred to the byp...

Page 6: ...o wait until the UPS fully dried inside out before proceeding to installation and use Otherwise they may be a risk of electric shock 4 Place the UPS near the utility power source outlet which supplies...

Page 7: ...t on the rear panel of the UPS to complete the connection procedure Note The length of the external battery cable is 1 6 m If users need a longer one please consult the distributor There is a limit to...

Page 8: ...ndicators The LED indicators contains Bypass indicator utility power indicator Inverter indicator Battery indicator The definition of each indicator is the same as LED panel refer to table 4 1 Table 4...

Page 9: ...oads connected to the UPS less than 100 capacity of the UPS 3 If the battery indicator blinks it indicates that no battery is connected to the UPS or battery voltage is too low You should check if bat...

Page 10: ...er another circularly When the battery is fully charged all the level icons are turned on 1 When operating in bypass mode the UPS beeps every 2 minutes If the Function key is pressedfor more than 2 se...

Page 11: ...switch to output page by pressing function button When a warning occurred the fault icon blinks every second and users can switch to the alarm display page shown as the figure 5 6 to check the warning...

Page 12: ...s shown on the front panel and no output is available from the UPS outlets system completely power down 2 Completely power down the UPS from Battery mode Press the OFF button persistently for more tha...

Page 13: ...rature between 15o C and 25o C 3 If the UPS has not been used for a long period charging is recommended at the intervals 3 months 4 Batteries should not be replaced individually 5 Under normal conditi...

Page 14: ...tributor or service center The 8 utility power LED blinks in normal mode Maybe reversed polarity L N of site wiring or disconnect with ground or the voltage between neutral wiring to protective ground...

Page 15: ...or Service center F05 On constantly Beep continuously Internal fault Please contact the distributor or Service center F06 On constantly Beep continuously Internal fault Please contact the distributor...

Page 16: ...every second Battery voltage low The UPS output will be cut off please switch to the backup power A03 Beep once every second UPS power on abnormal Check the battery of the UPS connected properly A05...

Page 17: ...Standard Charge current 1A 6 5A 1A 5 5A 1A 5 5A Crest factor 3 1 1 The output frequency synchronizes with the input frequency when the input frequency is in the range of 45Hz 55Hz 2 The output freque...

Page 18: ...IEC61000 4 4 LEVEL4 Surge IEC61000 4 5 LEVEL4 7 Specifications 7 2 Mechanical Item Normal range Ambient temperature 0 C 45 C Environment humidity 0 90 No condensation Altitude Lower than 1000m no dera...

Page 19: ...odel Intelligent monitor software CD 1 User Manual 1 Serial communication cable 1 UPS 1 Intelligent monitor software CD 1 Long backup time Model User Manual 1 External Battery Cable 1 Serial communica...

Page 20: ......

Page 21: ...Service center please Call 02 1863011 AUTO...

Reviews: