4. Operation (LCD model)                                                                                              

                            

4.1 Operation Display Panel

 

 

1. ON button:

    Pressing the ON button more than 1 second (buzzer beeps once), the UPS system is turned on.

  2. OFF button:

    By pressing this button more than 1 second (buzzer beeps once) turns off the UPS system whenever  

    the UPS run under the normal mode/battery mode.

  3. Function button

    The Function button provides the following functions:

    a)   Battery  self-  diagnosis:  When  the  UPS  ran  in  normal  mode,  pressing  this  button  more  than  2 

 

        seconds (buzzer beeps twice) can start the battery self-diagnosis.

    b)   Silence function in battery/bypass mode

        In battery/bypass mode, when the buzzer beeps, pressing and holding the function button for more than 

 

        2 seconds (buzzer beeps two times) can silence the buzzer. Press the button for more than 2 seconds 

 

        (buzzer beeps twice) again to resume the alarm function.

    c)   LCD display screen switch

        Pressing the function button for more than 1 seconds and less than 2 seconds (buzzer beeps once) 

 

        to switch LCD display screen.

  4. LED indicators

    The  LED  indicators  contains,  Bypass  indicator,  utility  power  indicator,  Inverter  indicator,  Battery 

 

    indicator. The definition of each indicator is the same as LED panel (refer to table 4-1). 

  

  

Table 4-1 Description of indicators

Data information area

8#Utility indicator

7#Bypass indicator

POWER ON

POWER OFF

Battery Level indicator 100%

Battery Level indicator   75%

Battery Level indicator   50%

Battery Level indicator   25%

Load Level indicator 100%

Load Level indicator   75%

Load Level indicator   50%

Load Level indicator   25%

Unit display area

Function

Current status display

Alam/Fault indicator

9#Inverter indicator

10#Battery indicator

Figure 4-1 LCD Display panel

 

No. Color 

Indicator 

Description

  7# 

Orange 

Bypass indicator

 

When the indicator on, it shows that the loading current 

  

 

 

is supplied from the utility power directly.

  8# 

Green 

Utility power indicator 

When the indicator on, it shows that the utility power is normal.

  9# 

Green 

Inverter indicator

 

When the indicator on, it shows that the load current 

  

 

 

is supplied from utility power or battery via the inverter.

 10# 

Orange 

Battery indicator

 

When the indicator on, it shows that the load current 

  

 

 

is supplied from battery via the inverter.

Summary of Contents for Venus Smart 1K

Page 1: ...HUPHOTIC CO LTD ENERGY WAVE CO LTD CHUPHOTIC ELECTRONICS CO LTD 949 Moo 9 Sumrong Nue Muang Samutprakarn Samutprakarn 10270 Tel 02 186 3011 Fax 02 186 3018 19 Website www chuphotic com E mail ups chup...

Page 2: ...g Inspection 4 3 2 Installation Notes 4 3 3 Cable Connection 4 5 4 Operation LCD model 6 10 4 1 Operation Display Panel 6 4 2 Operation Mode 6 8 4 3 Operating Instructions 9 10 5 Maintenance 10 11 5 1...

Page 3: ...Do not short the positive and negative electrodes of battery Otherwise it may cause electric shock or fire 6 Do not plunge or insert any objects into the air vents and other inlets 7 Do not store or...

Page 4: ...el Remark 1K With a 1A internal charger and 3 build in batteries of 12V 7AH 2K With a 1A internal charger and 6 or 8 build in batteries of 12V 7AH 3K With a 1A internal charger and 8 build in batterie...

Page 5: ...battery through the DC DC converter 5 Bypass It is very important in the UPS system In the event of a UPS fault that will not lead to UPS shutdown the load will be automatically transferred to the byp...

Page 6: ...o wait until the UPS fully dried inside out before proceeding to installation and use Otherwise they may be a risk of electric shock 4 Place the UPS near the utility power source outlet which supplies...

Page 7: ...t on the rear panel of the UPS to complete the connection procedure Note The length of the external battery cable is 1 6 m If users need a longer one please consult the distributor There is a limit to...

Page 8: ...ndicators The LED indicators contains Bypass indicator utility power indicator Inverter indicator Battery indicator The definition of each indicator is the same as LED panel refer to table 4 1 Table 4...

Page 9: ...oads connected to the UPS less than 100 capacity of the UPS 3 If the battery indicator blinks it indicates that no battery is connected to the UPS or battery voltage is too low You should check if bat...

Page 10: ...er another circularly When the battery is fully charged all the level icons are turned on 1 When operating in bypass mode the UPS beeps every 2 minutes If the Function key is pressedfor more than 2 se...

Page 11: ...switch to output page by pressing function button When a warning occurred the fault icon blinks every second and users can switch to the alarm display page shown as the figure 5 6 to check the warning...

Page 12: ...s shown on the front panel and no output is available from the UPS outlets system completely power down 2 Completely power down the UPS from Battery mode Press the OFF button persistently for more tha...

Page 13: ...rature between 15o C and 25o C 3 If the UPS has not been used for a long period charging is recommended at the intervals 3 months 4 Batteries should not be replaced individually 5 Under normal conditi...

Page 14: ...tributor or service center The 8 utility power LED blinks in normal mode Maybe reversed polarity L N of site wiring or disconnect with ground or the voltage between neutral wiring to protective ground...

Page 15: ...or Service center F05 On constantly Beep continuously Internal fault Please contact the distributor or Service center F06 On constantly Beep continuously Internal fault Please contact the distributor...

Page 16: ...every second Battery voltage low The UPS output will be cut off please switch to the backup power A03 Beep once every second UPS power on abnormal Check the battery of the UPS connected properly A05...

Page 17: ...Standard Charge current 1A 6 5A 1A 5 5A 1A 5 5A Crest factor 3 1 1 The output frequency synchronizes with the input frequency when the input frequency is in the range of 45Hz 55Hz 2 The output freque...

Page 18: ...IEC61000 4 4 LEVEL4 Surge IEC61000 4 5 LEVEL4 7 Specifications 7 2 Mechanical Item Normal range Ambient temperature 0 C 45 C Environment humidity 0 90 No condensation Altitude Lower than 1000m no dera...

Page 19: ...odel Intelligent monitor software CD 1 User Manual 1 Serial communication cable 1 UPS 1 Intelligent monitor software CD 1 Long backup time Model User Manual 1 External Battery Cable 1 Serial communica...

Page 20: ......

Page 21: ...Service center please Call 02 1863011 AUTO...

Reviews: