dIXEL

 

Installing and Operating Instructions 

1592027050

 

 

1592027050 XW60L RTC GB r1.0 27.06.2008.doc 

XW60L 

4/6 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 

dP2  Evaporator probe display 
dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real set point:

 it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUTS  

The first digital input 13-14 is enabled  with P3P = n. 
With P3P = n and i1F = i2F the second digital input is disabled 
The free voltage digital inputs are programmable by the “

i1F

” and i2F  parameters. 

8.1

 

GENERIC ALARM (i1F or i2F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the 

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.2

 

SERIOUS ALARM MODE (i1F or i2F =  bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.3

 

PRESSURE SWITCH (i1F or i2F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of 

activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

8.4

 

DOOR SWITCH INPUT  (i1F or i2F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 

= normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The alarm 

stops as soon as the external digital input is disabled again. With the door open, the high and low 
temperature alarms are disabled. 

8.5

 

START DEFROST (i1F or i2F = dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety 
time is expired. 

8.6

 

SWITCH THE AUXILIARY RELAY (i1F or i2F = AUS) 

With oA3 = AUS the digital input switched the status of the auxiliary relay 

8.7

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F or 

i2F=Htr)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.8

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.9

 

HOLIDAY DEFROST (i1F or i2F = HDF) –ONLY FOR MODELS WITH RTC 

This function enabled the holiday defrost setting. 

8.10

 

ON OFF FUNCTION (i1F or i2F = onF)  

To switch the controller on and off. 

8.11

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” and 

“i2P” 

parameters. 

i1P or i2P =CL

: the input is activated by closing the contact.

 

i1P or i2P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 
TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the dedicated 
connector. 

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used 
CAB/REP1(1m), CAB/REP2 
(2m), CAB/REP5 (5m), 

11.

 

INSTALLATION AND MOUNTING 

The controller 

XW60L

, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 

screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-

L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let the air circulate by the cooling holes. 

 

11.1

 

CUT OUT 

 

11.2

 

STEEL FINISHING MOUNTING  

1

1

2

2

3

3

4

4

RG-LX gascke

(optional)

 

12.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 
2,5 mm

for the digital and analogue inputs. Relays and power supply have a Faston connection 

(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power 
supply complies with the instrument’s requirements. Separate the probe cables from the power 
supply cables, from the outputs and the power connections. Do not exceed the maximum current 
allowed on each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

Summary of Contents for 6040 Series

Page 1: ...Refrigerated Pastry Showcase 6040 SERIES Maintenance And Use Manual CIAMspa 06081 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...or refrigerators freezers and ice machines 1 4 RESPONSIBILITY Ciam declines any responsibility relevant to damages on persons animals and or products in case of No respect of in force norms Installati...

Page 3: ...ong stock have not to be ascribed to the manufacturer 3 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 4: ...et in order to make easy any type of check and maintenance operations When the condensing units are external will be necessary a frame holder that has to be fixed in a proper way and eventually added...

Page 5: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 6: ...G ELEMENT SUCTION AIR GLASS HEATING ELEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME...

Page 7: ......

Page 8: ......

Page 9: ...s length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON...

Page 10: ...THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL user level by pressing SET n In HIDDEN MENU when a parameter is p...

Page 11: ...ture alarm delay 0 255 min time interval between the detection of an alarm condition and alarm signalling dAO Exclusion of temperature alarm at start up from 0 0 min to 23 5h time interval between the...

Page 12: ...TORING SYSTEMS The TTL serial line available through the HOT KEY connector allows by means of the external TTL RS485 converter XJ485 CX to connect the instrument to a monitoring system ModBUS RTU comp...

Page 13: ...ous cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 Pr2 COn Compressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe...

Page 14: ...50 min nu 13 0 rtc Sd3 3rd holiday defrost start 0 23h 50 min nu 21 0 rtc Sd4 4th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday de...

Page 15: ...standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are u...

Page 16: ...visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled...

Page 17: ...will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function all...

Page 18: ...XW20LS DIRECT CONNECTIONS OF LOAD Supply 120Vac or 24Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real tim...

Page 19: ...start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room...