dIXEL
Installing and Operating Instructions
1592027050
1592027050 XW60L RTC GB r1.0 27.06.2008.doc
XW60L
4/6
PbC Type of probe:
it allows to set the kind of probe used by the instrument:
PbC
= PBC probe,
ntc
=
NTC probe.
onF on/off key enabling: nu =
disabled;
oFF =
enabled;
ES = not set it
.
dP1 Thermostat probe display
dP2 Evaporator probe display
dP3 Third probe display
-
optional
.
dP4 Fourth probe display
.
rSE Real set point:
it shows the set point used during the energy saving cycle or during the
continuous cycle.
rEL Software release
for internal use
.
Ptb Parameter table code:
readable only
.
8.
DIGITAL INPUTS
The first digital input 13-14 is enabled with P3P = n.
With P3P = n and i1F = i2F the second digital input is disabled
The free voltage digital inputs are programmable by the “
i1F
” and i2F parameters.
8.1
GENERIC ALARM (i1F or i2F = EAL)
As soon as the digital input is activated the unit will wait for “
did
” time delay before signalling the
“
EAL
” alarm message. The outputs status don’t change. The alarm stops just after the digital input is
de-activated.
8.2
SERIOUS ALARM MODE (i1F or i2F = bAL)
When the digital input is activated, the unit will wait for “
did
” delay before signalling the “
CA
” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.3
PRESSURE SWITCH (i1F or i2F = PAL)
If during the interval time set by “
did
” parameter, the pressure switch has reached the number of
activation of the “
nPS
” parameter, the “
CA
” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is always
OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to
restart normal regulation.
8.4
DOOR SWITCH INPUT (i1F or i2F = dor)
It signals the door status and the corresponding relay output status through the “
odc
” parameter:
no
= normal (any change);
Fan
= Fan OFF;
CPr
= Compressor OFF;
F_C
= Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “
did
”, the door alarm is
enabled, the display shows the message “
dA
” and
the regulation restarts is rtr = yES.
The alarm
stops as soon as the external digital input is disabled again. With the door open, the high and low
temperature alarms are disabled.
8.5
START DEFROST (i1F or i2F = dEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety
time is expired.
8.6
SWITCH THE AUXILIARY RELAY (i1F or i2F = AUS)
With oA3 = AUS the digital input switched the status of the auxiliary relay
8.7
INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F or
i2F=Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.8
ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+ HES
(parameter) sum. This function is enabled until the digital input is activated.
8.9
HOLIDAY DEFROST (i1F or i2F = HDF) –ONLY FOR MODELS WITH RTC
This function enabled the holiday defrost setting.
8.10
ON OFF FUNCTION (i1F or i2F = onF)
To switch the controller on and off.
8.11
DIGITAL INPUTS POLARITY
The digital input polarity depends on the “
i1P
” and
“i2P”
parameters.
i1P or i2P =CL
: the input is activated by closing the contact.
i1P or i2P=OP
: the input is activated by opening the contact
9.
TTL SERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows by means of the external
TTL/RS485 converter,
XJ485-CX
, to connect the instrument to a monitoring system
ModBUS-RTU
compatible such as the X-WEB500/3000/300.
10.
X-REP OUTPUT – OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the dedicated
connector.
To connect the X-REP to the
instrument the following
connectors must be used
CAB/REP1(1m), CAB/REP2
(2m), CAB/REP5 (5m),
11.
INSTALLATION AND MOUNTING
The controller
XW60L
, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two
screws
∅
3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-
L). The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes.
Let the air circulate by the cooling holes.
11.1
CUT OUT
11.2
STEEL FINISHING MOUNTING
1
1
2
2
3
3
4
4
RG-LX gascke
(optional)
12.
ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to connect cables with a cross section up to
2,5 mm
2
for the digital and analogue inputs. Relays and power supply have a Faston connection
(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power
supply complies with the instrument’s requirements. Separate the probe cables from the power
supply cables, from the outputs and the power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable external relay.
N.B.
Maximum current allowed for all the loads is 20A.
12.1
PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
13.
HOW TO USE THE HOT KEY
13.1
HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the “
Hot key
” and push
o
key; the
"uPL"
message
appears followed a by flashing
“End”
3.
Push “
SET”
key and the
End
will stop flashing.
4.
Turn OFF the instrument remove the
“Hot Key”,
then turn it ON again.
NOTE
: the “
Err
” message is displayed for failed programming. In this case push again
o
key if you
want to restart the upload again or remove the “
Hot key
” to abort the operation.
13.2
HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a
programmed “Hot Key” into the 5 PIN receptacle
and then turn the Controller ON.
3.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Controller memory,
the “
doL
” message is blinking followed a by flashing
“End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the
“Hot Key”.
.
NOTE
the message “
Err
” is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the “
Hot key
” to abort the operation.
14.
ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and “COF”
“P2”
Evaporator probe failure
Defrost end is timed
“P3”
Third probe failure
Outputs unchanged
“P4”
Fourth probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
"HA2"
Condenser high temperature
It depends on the “Ac2” parameter