,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV

UHO  FRG 

UHO  FRG 

1592009030 XW271 GB_1.doc

                           

;:/  ;:/

3/4

O3

Auxiliary probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the

evaporator probe.

P2P Evaporator probe presence:

n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.

P3P Auxiliary probe presence: n= not present; y= present.
HES Temperature increase during the Energy Saving cycle : (-30,0°C 

÷

 30,0°C / -22÷86°F) sets the

increasing value of the set point during the Energy Saving cycle.

DIGITAL INPUTS

odc Compressor and fan status when open door:

no = normal;
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.

I1P

Door switch input polarity:
CL
 : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.

I2P

Configurable digital input polarity:
CL
 : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact

I2F

Digital input operating mode: configure the digital input function:
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;

  

dFr = Start defrost;
AUS = Relay AUX actuation;
Es = Energy Saving;
onF = remote On/OFF.

did  Time interval/delay for digital input alarm:(0

÷

255 min.) Time interval to calculate the number of the

pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines
the time delay between the detection and the successive signalling of the alarm.

SAA Set Point for anti-condensing heater: (-50,0÷110,0°C; -58÷230°F) defines the room temperature

setpoint  to switch on the anti-condensing heater.

OTHER

Adr  RS485 serial address (1÷247)Identifies the instrument address when connected to a ModBUS

compatible monitoring system.

Rel Release 

software: (read only) Software version of the microprocessor.

Ptb Parameter 

table: (read only) it shows the original code of the 

 parameter map.

Prd   Probes  display:  (read only) display the temperature values of the evaporator probe Pb2 and the

auxiliary probe Pb3.

Pr2  Access to the protected parameter list (read only).

DIGITAL INPUTS

The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the
second is programmable in seven different configurations by the “I2F” parameter.

DOOR SWITCH INPUT

It signals the door status and the corresponding relay output status through the “odc” parameter:

no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.

Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and
the display shows the message “dA”. The alarm stops as soon as the external digital input is disabled again.
During this time and then for the delay “dot” after closing the door, the high and low temperature alarms are
disabled.

CONFIGURABLE INPUT - GENERIC ALARM (EAL)

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm
message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL)

When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm message.
The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL)

If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of
the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation
are stopped. When the digital input is ON the compressor is always OFF.

CONFIGURABLE INPUT - START DEFROST (DFR)

It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired.

CONFIGURABLE INPUT - RELAY AUX ACTUATION (AUS)

This function allows to turn ON and OFF the auxiliary relay by using the digital input as external switch.

CONFIGURABLE INPUT - ENERGY SAVING (ES)

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter)
sum. This function is enabled until the digital input is activated.

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF)

This function allows to switch ON and OFF the instrument.

DIGITAL INPUTS POLARITY

The digital inputs polarity depends on “I1P” and “I2P” parameters.

CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact

INSTALLATION AND MOUNTING

Instruments XW270LXW271L shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two
screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). The

temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations,
corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate
by the cooling holes.

CUT OUT

165

150

31

+ 0.5

-0

+0

.5

-0

+ 1
-1

Ø3 x2

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD

C LIC K!

MOUNTING WITH KEYBOARD COVER OPENING UPWARD

C LIC K!

ELECTRICAL CONNECTIONS

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

for

the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the power
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a
suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.

PROBE CONNECTIONS

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is
recommended to place the thermostat probe away from air streams to correctly measure the average room
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most
ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost
termination.

TTL SERIAL LINE

The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line
ModBUS-RTU compatible as the 

monitoring system XJ500 (Version 3.0).

The same TTL connector is used to upload and download the parameter list of the “HOT KEY“.

Summary of Contents for CIAO GEL 12

Page 1: ...ICE CREAM DISPLAY CABINET CIAO series Maintenance And Use Manual CIAM SPA Viale dei Pini 9 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...freezers and ice machines For ETL marked cabinet UL471 CAN CSA C22 2 No 120 M91 NSF ANSI 7 2009 1 4 RESPONSIBILITY CIAM spa declines any responsibility relevant to damages on persons animals and or p...

Page 3: ...cle Refrigerating gas R 404A Glasses Heated side glasses hetaed front glass Standard internal compressor Type Hermetic single phase No 1 1 1 Nominal power W 600 725 2 x 560 Power current of display ca...

Page 4: ...ong stock have not to be ascribed to the manufacturer 5 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 5: ...the choice of piping diameter and insulation thickness has to be taken by specialised technical personnel who know specific parameters The choice of piping diameter and insulation thickness has to be...

Page 6: ...se the display cabinet has a dipper well it is necessary make the connection of its water outlet with the main water drain outlet besides it is necessary set a load water tube to the dipper well to th...

Page 7: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 8: ...evaporator blocked by frost Verify the efficiency of the gasket seal relatively to the glass superstructure Verify that the display area is not crossed by draughts Verify that backsliders or night bl...

Page 9: ...ronics Replace digital thermostat Defrost water missing Water drain pipes are blocked Remove the obstacle Defrost cycle is not efficient Verify the efficiency of control panel slave module sensor sole...

Page 10: ...LEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME HEATING ELEMENT FRONT GLASS LATERAL...

Page 11: ......

Page 12: ...L OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuousl...

Page 13: ...Remote display select which probe is displayed by the remote display XW REP P1 Thermostat probe P2 Evaporator probe P3 auxiliary probe 1r2 difference between P1 and P2 P1 P2 DEFROST tdF Defrost type...

Page 14: ...ore signalling the BAL alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated CONFIGURABLE INPUT PRESSURE SWITCH PAL If during the interval t...

Page 15: ...Power supply 230Vac or 110Vac 10 Power absorption 7VA max Display 3 digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compresso...