8.  DEFECTS AND REMEDIES 

 

DEFECT 

PROBABLE CAUSES 

POSSIBLE REMEDIES 

The unit does not work 

Automatic switch released due to 
absorption overload 

Re-start the automatic switch 

Main switch off 

Turn the main switch on 

Refrigeration switch off 

Turn the refrigeration switch on 

Electrical black-out in the building 

If  the  black-out  does  not  end  in  a  reasonable  time  frame,  it  become 
necessary to move the displayed product in another refrigerator 

The temperature inside the display 
area does not get enough cold 

The evaporator(s) is blocked by ice 
forming 

Operate  a  complete  defrost  cycle  after  having  displaced  the  products  in 
another refrigerator.Do not put the product back in the cabinet until the real 
defect has been identified 

The internal fans are damaged or not 
working 

Replace the damaged fans. If the fans are not damaged, an electrical defect 
must be identified. If the fans are replaced, the blades’ inclination have to be 
maintained unchanged 

Excess of internal ventilation 

Replace the fans and make sure that blades’ inclination is kept unchanged 

The pre-set temperature of the digital 
control panel is wrong 

Set the correct temperature 

The digital control is not working 

Replace the slave module or the temperature sensor, after you made clear 
which one is faulty  

The display area is crossed by draught or 
exposed to direct/reflected sunbeams 

Eliminate draughts and try to avoid sunbeams interference in any way 

Air condenser is clogged by dust or dirt 

Clean the condenser with accuracy 

The cooling air flow of the condenser is not 
sufficient 

Remove everything that might obstacle the air flow through the condenser 

Refrigerant gas not sufficient inside the 
cooling system 

Find  and  remove  the  leak  inside  the  system.  Refill  the  system  with  the 
refrigerant 

The cooling water flow of the water 
condenser is not sufficient 

Check that water supply is operating. In case it is, just regulate (or replace) 
the regulation valve 

The product gets too hard next to 
air outlet and too soft next to air 
intake 

Front evaporator blocked by frost 

Verify the efficiency of the gasket seal (relatively to the glass superstructure). 
Verify that the display area is not crossed by draughts. Verify that backsliders 
(or night blind) are always closed, peak hours excepted. Verify that internal 
ventilation  is  sufficient  and  that  the  product  does  not  exceed  10mm  above 
the pans level. Act accordingly 

Front evaporator blocked by ice 

All the a.m. checks are required  
Verify, in addition, the defrost cycle efficiency  

Back evaporator blocked by ice 

Verify  that  the  refrigerating  and  electric  systems  of  the  unit  are  working 
properly 

Internal fans are not efficient 

Restore the efficiency of the fans by replacing the damaged ones 

The basket seal of the glass 
superstructure is not sufficient 

Verify  the  seriousness  of  the  defect  and  make  sure  the  draughts  are 
minimized 

Some of the products tend to 
soften, while some other keep the 
right consistence 

The temperature inside the display area is 
not fit for the products that get too soft 

Since the storage temperature cannot be appropriate for any gelato product, 
based on different flavours and compositions, it is suggested to display only 
similar products together 

The compressor does not start or it 
does not hold operating 

There is no electrical supply 

Verify there is no black-out in progress. Turn all the power switches on. 

The supply tension is too low 

Verify that nominal tension at connecting clamps is 220V; a tension between 
198V and 242V will be acceptable. If the tension does not reach 198V, the 
compressor might have problems in starting. Verify the efficiency of electric 
installation including the connecting clamps to the compressor 

The pre-set temperature on the thermostat 
is too high 

If the preset temperature is higher than in the display area, the compressor is 
not  going  to  work.  Change  the  settings  if  you  verify  that  the  preset 
temperature is not enough low 

The intervention of the max pressure valve 
(where present) 

Identify the probable cause  among the following: 
The  air  condenser  is  blocked  -  The  cooling  fan  of  the  air  condenser  is  not 
working  -  The  room  temperature  is  too  high  -  Lack  of  cooling  water  in  the 
water condenser - The pressure valve is broken - Remove the cause 

 
 
 
 
 

Summary of Contents for CIAO GEL 12

Page 1: ...ICE CREAM DISPLAY CABINET CIAO series Maintenance And Use Manual CIAM SPA Viale dei Pini 9 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...freezers and ice machines For ETL marked cabinet UL471 CAN CSA C22 2 No 120 M91 NSF ANSI 7 2009 1 4 RESPONSIBILITY CIAM spa declines any responsibility relevant to damages on persons animals and or p...

Page 3: ...cle Refrigerating gas R 404A Glasses Heated side glasses hetaed front glass Standard internal compressor Type Hermetic single phase No 1 1 1 Nominal power W 600 725 2 x 560 Power current of display ca...

Page 4: ...ong stock have not to be ascribed to the manufacturer 5 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 5: ...the choice of piping diameter and insulation thickness has to be taken by specialised technical personnel who know specific parameters The choice of piping diameter and insulation thickness has to be...

Page 6: ...se the display cabinet has a dipper well it is necessary make the connection of its water outlet with the main water drain outlet besides it is necessary set a load water tube to the dipper well to th...

Page 7: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 8: ...evaporator blocked by frost Verify the efficiency of the gasket seal relatively to the glass superstructure Verify that the display area is not crossed by draughts Verify that backsliders or night bl...

Page 9: ...ronics Replace digital thermostat Defrost water missing Water drain pipes are blocked Remove the obstacle Defrost cycle is not efficient Verify the efficiency of control panel slave module sensor sole...

Page 10: ...LEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME HEATING ELEMENT FRONT GLASS LATERAL...

Page 11: ......

Page 12: ...L OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuousl...

Page 13: ...Remote display select which probe is displayed by the remote display XW REP P1 Thermostat probe P2 Evaporator probe P3 auxiliary probe 1r2 difference between P1 and P2 P1 P2 DEFROST tdF Defrost type...

Page 14: ...ore signalling the BAL alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated CONFIGURABLE INPUT PRESSURE SWITCH PAL If during the interval t...

Page 15: ...Power supply 230Vac or 110Vac 10 Power absorption 7VA max Display 3 digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compresso...

Reviews: