EN - 18
HYDROCIAT LW - LWP
1800BX
1800BX
HPS
2150BX
2150BX
HPS
2500BX
2500BX
HPS
2800BX
2800BX
HPS
Compressors
Voltage
3 ph / 50 Hz / 400 V (+10 % / - 10 %)
Maximum rated current
A
288 (2 x 144)
331 (187 + 144)
374 (2 x 187)
418 (2 x 209)
Start-up current (Star - Delta)
A
317
406
436
473
Breaking capacity
kA
25
Max. wire cross-section
mm²
2 x 240
Auxiliary circuit
Voltage
1 ph / 50 Hz / 230 V
Transformer capacity
VA
1600
Maximum rated current
A
4
Protection
rating
machine
IP 21
electrics box
IP 21
HYDROCIAT LW - LWP
3050BX
HPS
3500BX
HPS
3600BX
HPS
3900BX
HPS
4200BX
HPS
4500BX
HPS
4800BX
HPS
Compressors
Voltage
3 ph / 50 Hz / 400 V (+10 % / - 10 %)
Maximum rated current
A
445 (258 + 187) 515 (306 + 209) 516 (2 x 258) 564 (306 + 258) 603 (345 + 258) 651 (345 + 306) 690 (2 x 345)
Start-up current (Star - Delta)
A
587
718
636
757
821
849
871
Breaking capacity
kA
25
Max. wire cross-section
mm²
3 x 240
4 x 240
Auxiliary circuit
Voltage
1 ph / 50 hz / 230 V
Transformer capacity
VA
2000
Maximum rated current
A
5
Protection
rating
machine
IP 21
electrics box
IP 21
HYDROCIAT
LW - LWP
1800BX
(HPS)
2150BX
(HPS)
2500BX
(HPS)
2800BX
(HPS)
3050BX
HPS
3500BX
HPS
3600BX
HPS
3900BX
HPS
4200BX
HPS
4500BX
HPS
4800BX
HPS
500 V knife fuses, type aM size 1 (DIN 43620)
Fuse ratings
CP 1 A
160
250
250
250
315
400
315
400
250
250
250
CP 2 A
160
160
250
250
250
250
315
315
315
400
250
Handle to use for inserting and
removing fuses (supplied)
Compressor fuses
Starting current of largest comp maximum current of other compressors at 50% load.
Cable selection rated current = sum of maximum rated currents indicated in tables above.
18.2 Electrical specifications