background image

EN - 20

If the system needs to be opened just after shutting down the 
compressor, e.g. to clean the oil strainer, be sure to let the oil 
cool down for long enough so that any oil splashes no longer 

pose any hazard.
A temperature of less than 35°C is recommended.

-  Containers must be stored with their caps on. Avoid using oil 

from an opened container stored under incorrect conditions.

20.1.4 Refrigerants - general information

 

Always remember that refrigeration systems contain 
pressurised liquids and vapours.

-  All necessary measures must be taken when partially opening 

the system: Make sure that there is no pressure in the part of 
the circuit concerned.

-  Partial opening of the primary refrigerant circuit will cause 

a certain quantity of refrigerant to be released into the 
atmosphere.

-  It is essential to keep the amount of lost refrigerant as low 

as possible by pumping the charge and isolating it in another 
part of the system.

-  The refrigerant and lubricating oil, and the low-temperature 

liquid refrigerant in particular, may cause inflammatory 
lesions similar to burns if they come into contact with the skin 
or eyes.

   Always wear protective eyewear, gloves and other protective 

equipment when opening pipes or tanks liable to have 
liquids in them. Store unused refrigerant in the appropriate 
containers and limit the amounts stored in mechanical rooms.

-  Cylinders and tanks of refrigerant must be handled with care 

and signs warning users of the related poisoning, fire and 

explosion  hazards  must  be  clearly  visible.  Refrigerant  that 

reaches the end of its life must be collected and recycled in 
accordance with applicable regulations.

20.1.5 Halocarbon and hydrofluorocarbon refrigerants

Although non-toxic, vapours from halocarbon and 

hydrofluorocarbon  refrigerants  are  still  hazardous  because 

they are heavier than air and can force the latter out of the 
machine rooms.
If refrigerant is accidentally released, ventilate the room with 
fans. Workplace exposure levels must be kept to a practical 
minimum, and must never exceed the recognised threshold of 
1000 ppm (particles per million) for an 8-hour working day and 
a 40-hour working week.
Although halocarbon and hydrofluorocarbon refrigerants are not 
flammable, keep them away from open flames (e.g. cigarettes, 

etc.),  as  temperatures  of  over  300°C  cause  their  vapours  to 

break down and form phosgene, hydrogen fluoride, hydrogen 
chloride and other toxic compounds. These compounds may 
produce severe physiological consequences if accidentally 
inhaled or swallowed.

20.1.6 Servicing

-  For units used seasonally, note down the operating readings 

and perform the checks indicated in the table in section 
20 Servicing and maintenance, at least twice a year and 
systematically whenever the unit is activated.

● Weekly checks

With the unit running at full capacity, check the following 
values:
-  Check the entire installation for traces of water or oil under or 

around the unit, and for any unusual noises.

- LP compressor suction pressure,
- HP compressor discharge pressure,

 

The water inlet and outlet temperatures in 

 

the exchangers

-    The charge via the liquid sight glass and the condition of the 

charge using the coloured indicator on the sight glass

-  The oil level and its appearance. If the colour changes, check 

the quality.

- Keep the unit clean
- Also check whether the safety devices operate correctly.

● Monthly checks

-  Check all the values listed in the "Operating readings" table 

on the previous page.

-  Perform a corrosion check on all the metal parts. (Frame, 

casing, exchangers, electrical boxes etc.)

-  Make sure that the insulating foam is not detached or torn.
-  Check the energy transfer fluids for any impurities which 

could cause wear or corrosion in the exchanger.

- Check the circuits for leaks.
-  Check whether the safety devices and the expansion valve(s) 

operate correctly

● Annual checks

 

Carry out the same inspections as during 

 

the monthly checks.

- Check the evaporator pressure drop (re-check after any 
cleaning).
- Check the sealing of the compressor/separator discharge 
check valve, and clean or replace the valve if necessary.
-  Test the oil for contaminants (annually or every 5000 hours): 

If acid, water or metal particles are detected, replace the oil 
in the corresponding circuit and the dryer.

-  If the whole oil load is being changed, use only new oil of the 

same grade as the original oil, which has been stored in a 
hermetically sealed container until loading. (see section 12 
Main components of the refrigerating circuit).

-  Check the filter dryer for clogging (measure the difference 

in the temperature of the pipes at the dryer inlet and outlet).

-  Check the electrical connections to ensure they are tight and 

in good condition.

-  

Check the insulation of the motor and the resistance 

 

of the coils.

- Clean the water filter and vent air from the circuit.
-  Clean the exchangers and check the pressure drop in each.
- Check the operation of the water flow switch.
- Check the water quality or condition of the coolant.

- Check the antifreeze concentration (MEG or PEG)

-  Check the electrical box for water seepage.
-   Check the condition of the contacts and the current at full load on  

all three phases.

-  Disconnect all the cables.
NB: The cleaning intervals are given as a guide and should be 
adapted to each installation.

20.1.7 Disassembling the compressor

The compressor is fastened to the platform by 4 screws 

 

with diameter 16 or 20 mm, according to the compressor size.

Warning:

 Do not tighten the compressor screws to a torque 

greater than 13 Nm ± 1 for HYDROCIAT LW and LWP. If you 
do not have a torque wrench, tighten them until they are snug 
then tighten a further ¾ turn.

IMPORTANT:

To ensure your unit runs smoothly and to obtain service 

under the warranty, take out a maintenance contract with 

your installer or an approved maintenance company.

Summary of Contents for HYDROCIAT 1800BX

Page 1: ...Instruction manual 01 2015 NA 01 29 I version B HYDROCIAT LW LWP...

Page 2: ......

Page 3: ...10 16 CONTROL AND SAFETY DEVICES 11 16 1 Electronic control and display module 11 16 2 Main functions 11 16 3 Safety device management 11 16 4 Electronic expansion valve 12 16 5 Oil safety 12 16 6 Set...

Page 4: ...he plate on the unit to ensure that it is the correct model Please include the identification number in all correspondence with CIAT 4 SAFETY INSTRUCTIONS To prevent accidents while installing activat...

Page 5: ...tting flexible sleeves on the hydraulic piping Have an analysis carried out by an acoustics engineer 8 HANDLING AND POSITIONING These machines must be unloaded and positioned by a specialist handling...

Page 6: ...91 4759 5106 5274 5293 5342 5362 Weight in operation Kg 3360 3380 3800 3820 4110 4130 4120 4140 5064 5275 5502 5812 5820 5905 5925 HYDROCIAT LW LWP 1800BX HPS 2150BX HPS 2500BX HPS 2800BX HPS 3050BX H...

Page 7: ...rate can be a fouling factor an excessively high flow rate can cause erosion phenomena 11 LOCATION OF THE MAIN COMPONENTS LW LWP 1800BX to 2800BX LW LWP 3050BX to 4800BX HYDROCIAT LW LWP T minimum C 5...

Page 8: ...s diagram shows the positions and dimensions of the water inlets and outlets on the exchangers Follow the requirements below when making these connections Ensure the inlet and outlet pipes are connect...

Page 9: ...be secured to the wall of the building and must not place any additional load on the unit Using untreated or incorrectly treated water may cause corrosion or erosion or the formation of scale algae or...

Page 10: ...STALLATION ANTIFREEZE PROTECTION The table and the curves below indicate the minimum percentages of glycol with which the system must be provided depending on the freezing point WARNING The glycol con...

Page 11: ...nnect the protective conductor to the earth terminal Make the terminal block X2 customer connection Connect the general fault display dry contact and the automatic operation control dry contact where...

Page 12: ...O Circuit 1 available Input C Circuit 1 unavailable 16 Circuit 2 fault On Off output Input O Circuit 2 available Input C Circuit 2 unavailable 17 18 Fault display On Off output Input O Fault Input C N...

Page 13: ...the compressor s in the refrigerating circuit concerned is cut off and the fault is indicated by an LED on the controller console The HP pressure switches are reset manually thus any fault will be cl...

Page 14: ...or 60 C depending on the unit These temperatures correspond to the least favourable situation the unit could be subjected to excluding an external fire The LP side pipes are sized for the maximum allo...

Page 15: ...me installation principle as circuit 1 CIRCUIT 1 CONDENSER Outdoor sensor LW LWP 1800BX to 2800BX with electronic expansion valve B1 BP1 BP2 B3 B2 FS B9 B15 BP1 BP2 BP3 BP4 B7 B12 HPS HPS P P HP1 HP2...

Page 16: ...red red for shipment Screws to be removed Check that the discharge valves and liquid outlet valves are open Close the drain valve under the evaporator After opening the water circuit valves make sure...

Page 17: ...ion in the correct direction swap the two power supply phases Check the compressor discharge temperature using a contact sensor Check all safety devices to make sure they operate correctly During acti...

Page 18: ...C 8 C 150 C Min max water flow m3 h 50 150 Hydraulic connection VICTAULIC DN 150 Design pressure water side bar 10 refrigerant side bar 13 Test pressure water side bar 14 3 refrigerant side bar 26 Wa...

Page 19: ...ax water outlet temperature C 8 C 150 C Min max water flow m3 h 80 231 80 246 80 231 80 246 80 293 Hydraulic connection VICTAULIC DN 200 Design pressure water side bar 10 refrigerant side bar 20 Test...

Page 20: ...45 258 651 345 306 690 2 x 345 Start up current Star Delta A 587 718 636 757 821 849 871 Breaking capacity kA 25 Max wire cross section mm 3 x 240 4 x 240 Auxiliary circuit Voltage 1 ph 50 hz 230 V Tr...

Page 21: ...ems must be carried out by a qualified authorised technician Any opening or closing of a shut off valve must be carried out with the unit off The liquid valve located just before the dryer must always...

Page 22: ...ith the unit running at full capacity check the following values Check the entire installation for traces of water or oil under or around the unit and for any unusual noises LP compressor suction pres...

Page 23: ...safety disconnection check bar Preliminary advice Faults detected by the safety devices are not necessarily caused by a sudden change in the measurement being monitored Taken regularly readings shoul...

Page 24: ...nding fault Start ups too close together short cycle protection disrupted Overload protection disrupted or defective Power supply voltage too low Current limiter malfunction Set the correct time betwe...

Page 25: ...ng more than 300 kg of refrigerant Implementation of leak detection system For all systems which contain over 3 kg of refrigerant 2 kg in France users are required to keep a log of the quantities and...

Page 26: ...ed J Water filter Compulsory K Water hose Compulsory L Thermometer well M Hydraulic 3 way valve N Cleanable exchanger O Safety valve A Chilled water or hot water circuit C Water filling D Expansion ve...

Page 27: ......

Page 28: ...erves the right without notice to proceed with any technical modification Dieses Dokument ist keine Vertragsunterlage Da wir st ndig bem ht sind unser Material noch weiter zu verbessern beh lt sich CI...

Reviews: