Supply valve
CHARGING UNIT
Flow regulator
In case of a fault with the humidifier (no steam produced), check the water conductivity: it must be between 350 and 1250 µS/cm.
If frequent descaling is necessary, check the water hardness. It should be 15°f<TH<30°f.
Water drainage
Drain pump
Water top-up
Filling solenoid valve
13.4 - Fans
Sizes CW 40 to 100
Fitting UNDER
FMA access hatches (A)
-
Remove the screws on the fan access hatches and remove the hatches. (Figure A)
13 - MAINTENANCE
EN-31 MAGISTER
®