CIB UNIGAS - M039208CA
34
Light oil filter maintenance
For correct and proper servicing, proceed as follows:
1
shut off fuel in the line section being serviced;
2
unscrew the tray;
3
remove the filter cartridge from its support and wash it with petrol or replace if necessary; check seal O-Ring, replace if necessary;
4
reassemble the tray and restore fuel flow.
Removing the combustion head
z
Remove the top cover C;
z
remove the photoresistor from its seat;
z
unscrew the revolving connectors (E in Fig. 20) on the fuel pipes (use 2 spanners to avoid loosening the connections attached to
the distributor block);
z
loosen the screw VRT to free the threaded rod AR, then screw out the 2 screws V holding the washer R and the screw VRT in posi-
tion;
z
remove the whole assembly as shown in Fig. 19.
Note: to replace the combustion head reverse the procedure described above.
Fig. 19
Removing the gun
1
Remove the combustion head, as described on the previous paragraph;
2
slacken the screw VB
3
remove the lance with the nozzle holder
4
to replace the combustion head reverse the procedure described above.
C
AR
VRT
R
VB
E
Fig. 20
Summary of Contents for TN 1030
Page 2: ......
Page 20: ...CIB UNIGAS M039208CA 20 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 23: ...CIB UNIGAS M039208CA 23 z BERGONZO NOZZLES Fig 11...
Page 24: ...CIB UNIGAS M039208CA 24 Fig 12...
Page 25: ...CIB UNIGAS M039208CA 25 Fig 13...
Page 26: ...CIB UNIGAS M039208CA 26 Fig 14...
Page 43: ......