Adjusting air and gas flow rates
Gas Filter
The gas filters remove the dust particles that are present in the gas, and prevent the elements at risk (e.g.: burners, counters and regu-
lators) from becoming rapidly blocked. The filter is normally installed upstream from all the control and on-off devices.
Actuator
The actuator provided can be either Berger STM30../Siemens SQM40.. (see page 25) or Siemens SQL33.. (see page 27).
VPS504 Gas proving system
The VPS504 check the operation of the seal of the gas shut
off valves. This check is carried out as soon as the boiler
thermostat
TAB
gives a start signal to the burner, creating,
by means of the diaphragm pump inside it, a pressure in the
test space of 20 mbar higher than the supply pressure.
When wishing to monitor the test, install a pressure gauge
into the pressure supply point
PA
.
If the test cycle is satisfactory, after a few seconds the con-
sent light
LC
(yellow) comes on. Otherwise, the lockout light
LB
(red) comes on.
To restart, it is necessary to reset the appliance by pressing
the pushbutton
LB
.
LC
LB
PA