circuit (contact XIV) and during safety time (contact IV)
(3)
Do not press EK for more than 10 seconds
Programmer diagram
t1
pre-ventilation time
t2
safety time
*t2
'1st safety time
t3
pre-ignition time
*t3
'pre-ignition time
t4
interval for creating current between terminals 18 and 19
*t4
'interval for creating current between terminals 17 and 19
t5
interval for creating current between terminals 19 and 20
t6
post-ventilation time
t7
interval between startup consent and current created at
terminal 7
t8
duration of start-up
*t9
2nd safety time
t10
interval before air pressure monitoring begins
t11
damper opening travel time
t12
damper closure travel time
t13
permissible post-combustion time
t16
initial delay of damper OPEN response
t20
interval before programmer automatically stops
* These times are valid with the use of a series 01 safety device for moni-
toring burners with intermittent pilot lighter.