C.I.B. UNIGAS - M039175CD
6
BURNERS FEATURES
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical Specifications
*
NOTE ON THE BURNER WORKING SERVICE:
for safety reasons, one controlled shutdown must be performed every 24 hours of
continuous operation.
Type
RX90
Model
M-. PR. S. *. A. 1. 80
(1) (2) (3) (4) (5) (6) (7) (8)
(1) BURNER TYPE
RX90 - RX91
(2) FUEL
M - Natural gas
(3) OPERATION
(
Available versions)
PR - Progressive MD - Fully modulating
(4) BLAST TUBE
S - Standard L - Extended
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard
(7) EQUIPMENT
1 = 2 gas proving system
8 = 2 gas proving maximum gas pressure switch
(8) GAS CONNECTION
see Specifications
50 = Rp2
65 = DN65
80 = DN80 100 = DN100
BURNER TYPE
RX90
RX91
Output
min - max kW
288 - 1480
674 - 2008
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.-max. (Stm
3
/h)
30.5 - 157
71 - 213
Gas pressure
(see Note 2)
Power supply
400V 3N~ 50Hz
Total power consumption
kW
3.5
4.5
Electric motor
kW
3
4
Approximate weight
kg
250
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50 Connection
ØValves / Connections
50 / Rp 2
Gas train 65
ØValves / Connections
65 / DN65
Gas train 80
ØValves / Connections
80 / DN80
Gas train 100
ØValves / Connections
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
NOx emissions
≤
80 mg/kWh
(Class 3 - EN676
- 2008
)
Note1:
all gas flow rates are referred to Stm
3
/h (1013 mbar pressure, 15 °C temperature) and are valid for G20 gas (net calori-
fic value: 34.02 MJ/Stm
3
).
Note2:
Maximum gas pressure = 500mbar (with Siemens VGD gas valves).