background image

Current-source Analog Output Blocks

June 2002

                   GFK-0691D

4

Block Operation ________________________________

A Current-source Analog Input block has six independent inputs.

Input channels use voltage to frequency converters and counters to
translate analog currents to a digital value.  This value is converted
by the block to engineering units before it is  sent to the CPU.  A
diagram of an input circuit is shown below.

EXC

24VDC

Processor

16 Bit

Counter

V to F

Opto
Isol.

100

COM

GND

Case
Ground

47

Filter

IN

Each input circuit has a 24 volt current loop power supply, capable
of providing 25mA of current.  Each input is isolated from all other
circuits on the block.  Input accuracy is 0.1%.  Input conversion time
can be selected to provide the appropriate combination of noise
rejection and input resolution.  Conversion times are programmable
from 16ms to 400ms.  Resolution increases as the conversion time
is lengthened.  Input resolution is 1µA for 200ms conversion time.

Upper and lower alarm limits can be programmed for each input
circuit.  If either limit is exceeded, the block indicates a fault and
sends a message to the Hand-held Monitor and CPU.

The following illustration shows the input excitation current derating
versus temperature. The maximum excitation current per channel is
25mA.

30

60

90

120

0

10 20 30 40 50 60 70

150

temperature in degrees C

maximum excitation current

per block in milliAmps

Diagnostics _________________________________

The block’s advanced diagnostics provide the messages listed below.
Fault messages can be cleared from the Hand-held Monitor or the CPU.

Input Open Wire:

  Input current is below 2mA.

Input High Alarm:

  Input exceeds high alarm level.

Input Low Alarm:

  Input exceeds low alarm level.

Input Overrange:

  Signal exceeds 25mA.

Input Underrange:

  Current is negative, or 0mA.

Configuration _________________________________

First, the block must be configured with a Hand-held Monitor to:

 

Enter its Device Number (serial bus address).

 

Enter its Reference Number (required only for IC600 and IC550
series PLCs only).

The rest of the features can be configured either using a Hand-held
Monitor, or by sending a Write Configuration datagram to the block from
the host.

Note:

 

 

If a block is configured offline, it must be properly grounded and

have a 75 Ohm resistor installed across its Serial 1 and Serial 2
terminals. See the 

Discrete and Analog I/O Blocks User’s Manual

 for

instructions.

Feature

Circuit

/Block

Factory

Setting

Selections

Device Number

Block

null

0 to 31 (must be selected)

Reference Address

Block

none

Depends on host CPU type

Baud Rate, Kbd

Block

153.6 std 153.6 std, 153.6 ext, 76.8, 38.4

Report Faults

Circuit

yes

yes/no

Channel active

Circuit

active

 active/inactive

BSM Present

Block

no

yes/no

BSM Controller

Block

no

yes/no

CPU Redundancy

Block

none

none/standby

Input conversion time

Block

400ms

16 to 400ms

Input Scaling

Circuit

1µA per

eng unit

+/-32767 eng units

0 to +25000µA

Low Alarm

Circuit

0

+/-32767 eng. units

High Alarm

Circuit

+25000

+/-32767 eng. units

Configuration Protection

Block

disabled

enabled, disabled

Summary of Contents for ic660bba026

Page 1: ...ce 6 Inputs http www cimtecautomation com parts p 14421 ic660bba026 aspx Provides the wiring diagrams and installation guidelines for this GE Series 90 30 module For further information please contact Cimtec Technical Support at 1 866 599 6507 sales cimtecautomation com ...

Page 2: ...s 115 VAC 125 VDC Current Source Analog Input Block IC66 BBA106 Terminal Assembly IC66 TBA106 Electronics Assembly IC66 EBA106 24 48 VDC Current Source Analog Input Block IC66 BBA026 Terminal Assembly IC66 TBA026 Electronics Assembly IC66 EBA026 Block Specifications Size height x width x depth 8 83 22 44cm x 3 56 9 05cm x 4 42 11 23cm Weight 4 lbs 1 8 kg LEDs I O Block Unit OK I O Enabled BSM Cont...

Page 3: ...een blocks Mount the block by drilling two screw or bolt holes for 8 32 hardware Position the block so that the notches in the upper and lower flanges line up with the mounting holes Mount the block using 8 32 screws Use star washers to provide ground integrity Grounding The block s mounting screws must not be used as the only means of grounding the block Connect the green ground screw on the bloc...

Page 4: ...ws at the top and bottom of the block 2 Using a Block Puller IC660BLM507 engage the tabs in the first vent slots Move the tool to the center of the block and squeeze the handle 3 Pull the Electronics Assembly upward Warning If power is applied to the field terminals power is also exposed on the connector pins at the base of the Terminal Assembly and electrical shock hazard exists Do not touch the ...

Page 5: ...___________________________ The block s advanced diagnostics provide the messages listed below Fault messages can be cleared from the Hand held Monitor or the CPU Input Open Wire Input current is below 2mA Input High Alarm Input exceeds high alarm level Input Low Alarm Input exceeds low alarm level Input Overrange Signal exceeds 25mA Input Underrange Current is negative or 0mA Configuration ______...

Reviews: