3.3.- STORAGE FOR LONG PERIODS
If the device is not installed after receipt, the following recommendations must be observed to
keep the device in a good state:
Keep the device in a dry atmosphere and at a temperature of between -20ºC and 50ºC.
Avoid exposure to direct sunlight.
Keep the device in its original packaging.
If the active filter is stored for a long time disconnected from the mains, a specific process must
be applied to restore the internal dielectric layers of the DC bus capacitors.
Table 10
shows the
recommendations for starting the device, according to the length of its storage period.
Table 10: Start-up process, according to storage time�
Storage time
Process
< 1 year
No special treatment required.
> 1 year
Connect the
AFQm
to the mains at least one hour before
starting up the device. Power the device and leave it in
STOP mode
3.4.- INSTALLATION
3�4�1�- WALL-TYPE AFQm
The Wall-type
AFQm
has a number of holes on the top and bottom of the device,
Figure 4,
to
facilitate transport and installation of the device.
These holes can be used as attachment points for external manipulation tools, or a bar (not
included) can be passed through them to improve transport and installation of the device.
Figure 4: Holes to facilitate transport and installation�
The device must be fixed vertically to a wall or support.
Use 4 fixing screws with a diameter of
8 mm
, suitable for the chosen wall or support.
Summary of Contents for AFQm Series
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Page 2: ...2 AFQm Instruction Manual...
Page 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Page 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 106: ...106 AFQm Instruction Manual...
Page 107: ...107 Instruction Manual AFQm...