64
AFQm
Instruction Manual
The phase balancing option in
AFQm-3WF-xxxx
works in unbalances produced
by loads connected between phases in three-phase mains without neutral. The
AFQm-3WF-xxxx
does not compensate unbalances produced by single-phase
loads connected between phase and neutral. Use a
AFQm-4WF-xxxx
to correct
this type of unbalances.
Priority
Enable this option so that the device prioritises the functions in case of filter current saturation
due to overload:
With the function
enabled
, the current balancing between phases and the reactive current com-
pensation is prioritised over the harmonic filtering.
With the function
disabled
, priority is given to the current harmonic filtering and power factor
correction and overload balancing are penalised.
Table 22: Order of priorities
Priority
Order of priorities function
Disabled
Enabled
+
Harmonic filtering
Phase balancing
Power factor correction
-
Phase balancing
Power factor correction
Harmonic filtering
Reactive
Enable this function so that the device compensates the reactive energy or corrects the dis-
placement power factor, cos Φ.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration
values
Summary of Contents for AFQm Series
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Page 2: ...2 AFQm Instruction Manual...
Page 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Page 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 106: ...106 AFQm Instruction Manual...
Page 107: ...107 Instruction Manual AFQm...