66
AFQm
Instruction Manual
●
Min current
The minimum load current to start the active filter is configured with this parameter. Minimum
current feature is used to increase the system efficiency, by stopping the filter when required.
The
AFQm
will stop when the load current is below the entered value and will start when it is
higher.
Range of values:
Minimum value:
0 A
Maximum value:
5000 A
● Current limit
This parameter allows the maximum power of the active filter to be limited. The value is config
-
ured as a percentage with respect to the device's rated power.
Range of values:
Minimum value:
20%
Maximum value:
100%
● Cos ɸ
This parameter allows select the cos ɸ that the active filter must obtain.
Range of values:
0.7 ... -0.7
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration
values.
7.7.- TRANSFORMER CONFIGURATION
Note:
This screen is not visible on the
“slave”
devices.
The transformers that will be installed with the device are configured in this screen,
Figure 70
:
Figure 70:
Configuration screen: Transformer configuration.