42
DHC-96 CPM 1500
Instruction Manual
The format of the parameter is shown in
Table 18:Format of the parameter: Digital inputs�
Register 1
Register 2
Digital input 1
0001:
Closed
0000:
Open
Digital input 2
0001:
Closed
0000:
Open
6�3�4�- REMOTE CONTROL OUTPUT (Relay output)
All the addresses of Modbus memory are in Hexadecimal.
For these variables is implemented the
Function 0x05�
Table 19: Modbus memory map (Table 5)
Parameter
Format
Address
Value
Remote control, Output relay 1
bit
0000
0:
Open
1:
Closed
Remote control, Output relay 2
bit
0001
0:
Open
1:
Closed
Función 0x0F,
multiple relay control:
Table 20: Modbus memory map (Table 6)
Parameter
Address
Register
Remote control
0000
2
The format of the parameter is shown in
Table 21:Format of the parameter: Remote control�
Register 1
Register 2
Relay 1
0001:
Closed
0000:
Open
Relay 2
0001:
Closed
0000:
Open
6�3�5�- DELETING VALUES
All the addresses of Modbus memory are in Hexadecimal.
The
Function 0x0E
is available to delete the maximum, minimum and totaliser values.
Address
Function
Initial relay
address
Password
ID reset
ID value
CRC
Peripheral No.
0E
AACC
1111
ID reset
FF
xxxx
The
ID reset
value determines which values will be deleted:
Table 22: ID reset�
Parameter
ID reset
Maximum and minimum values
0x03
Electric charge totalisers
0x02
Energy totalisers
0x01
Summary of Contents for DHC-96 CPM
Page 1: ...INSTRUCTION MANUAL DC Multimeter DHC 96 CPM 1500 M331B01 03 22B...
Page 2: ...2 DHC 96 CPM 1500 Instruction Manual...
Page 50: ...50 DHC 96 CPM 1500 Instruction Manual 10 CE CERTIFICATE...
Page 51: ...51 Instruction Manual DHC 96 CPM 1500...
Page 52: ...52 DHC 96 CPM 1500 Instruction Manual...