3.4.-CONNECTION OF THE CAPACITOR BANK TO THE MAINS
Check that the rated voltage of the capacitor bank matches the voltage between
phases of the grid to which it is being connected.
Also check the operating circuit voltage (contactors).
(See
For feeding cables into the capacitor bank cabinet, always and only use the cable
entry points available for this purpose.
All models have a cable entry point on the bottom (base of the cabinet) as well as
a cable entry point on the side.
shows the cable entry points of the
OPTIM FRS P&P
models.
shows the cable entry points of the
OPTIM FR P&P
models.
If another part of the cabinet is cut out to be used for cable entry, the CIR
-
CUTOR manufacturer's guarantee shall be rendered void
.
Do not cut holes in other parts of the cabinet for feeding cables through or for
installing support brackets.
It may produce trimmings that can cause short-circuits.
Figure 4:
Cable entry points of the OPTIM FRS P&P models.
11
Instruction Manual
OPTIM FRS/FR P&P series