Code
Type
Sensivity (A)
Tripping delay (s)
Communications
P24642
RGU - 10 MT
0,03-0,1-0,3-0,5-1-3
by direct adjustment
5-10-30 by
SETUP
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
by direct adjustment
3-5-10 by
SETUP
No Available
P 2 X X X X 0 0 X
Código
Code
Código interno
Internal code
Tensión de
alimentación
Power supply
230 V a.c.
110 V a.c.
0
1
RGU-10 MT Electronic earth leakage protection relay with self-reclosing system
For instance, RGU-10 MT supplied by 110 V a.c.
GENERAL DESCRIPTION
- Device with programmable differential relay with self-reclosing system. Symbol in LCD.
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a
WG
/
WGS
Series external , toroidal current transformer.
- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer
WG/WGS
by means inductive test.
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
DESCRIPTION LED AND BUTTONS.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
INDICATION BY LED AND DISPLAY.
-
TRIP RELAY.
LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
-
BETWEN RECLOSURES.
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
-
LOCKED BY RECLOSURES
.
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
-
No OF RECLOSURES.
By short press on
PROG
the display shows the number of reclosures by
earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press
REC
button.
RECLOSING THE EQUIPMENT.
- BY
TRIP
/
LOCKED BY RECLOSURES
1. Automathic (earth leakage, short ciruit-overload faults or manual). Enabled.
2. Manual reclose by pushing button
RESET
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
RELAY PARAMETERS SETTING
(
t
,
I
y std/+ )
d
d
-
,
t
.
d
SETTING TRIP DELAY
The message and two values appear on the screen after
pressing the
button. The lowest value indicates the current set value and the highest is the
t
d
values to be configured which are displayed by pressing
The selected value to be saved is
.
displayed by showing the message
SAVE.
-
,
I
.
I
. .
d
d
SENSITIVITY SETTING
The same operation as above setting is carried out by pressing
- SIGNALLING CONTACTS RELAY STATE, std/+
. Select the default position of the relay contacts
7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the symbol in display.
- SELF-RECLOSING SYSTEM, REC
. In reclosure partial numbers by press
REC
button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.
Tripping cause
Message display
Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
TESt
EXT
DIF / valor
MAG
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection
M98205801-03-21A
P24642001
PARAMETERS BY
DIRECT ADJUSTMENT
-DELAY SETTING
-
SETUP
ROTATION
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
REC
SREC No RECLOSURES TIME SEQUENCES RESET TIME
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
SREC No RECLOSURES TIME SEQUENCE RESET TIME
RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT
- Tipo
Relay type: Electronic class A. High frequency current filtering.
- Rated power supply voltage
: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA
-
:
Connections
2
0,127 - 2,082 mm
Permissible cable section:
- Reclosing type: Authomatic, RESET button or by cutting power supply.
-
: -10ºC / 50ºC
Operating temperature
Recommended tightening torque: 0.5-0.6 Nm
TECHNICAL FEATURES
: 250/230 V a.c.
Rated voltage/Maximum switching voltage
Maximun Voltage: 275 Va.c.
-
13-14-15, 7-8-9 and 5-6
Switch Output contact features
: 6/10 A a.c.
Rated current/Maximum instant current
Length of cable to strip: 7 mm
AC: 2,500 V·A
Rated load in
Input not using optocoupler
-Characteristics input remote Trip/Reclose 1-2
Contacts protected by varistor
- Varistor Features
REC
REC
MT
WARNING: The reclosing sequences marked by are only for motorized circuit breakers with or
without trip coil. I >63 A.
N
Capacity:
Maximun DC Load Breaking
Maximun opening current
Electrical useful life for AC
loads: No of cycles
MAG
¡ IMPORTANT !
The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
verifies the relay trips the protection. It recloses only by manual pressing RESET button.
0 DISABLED
1 2 1 minute 30 minutes
2 2 1 minute 60 minutes
3 2 90 s 30 minutes
4 2 90 s 60 minutes
5
2 3 minutes 30 minutes
6 ... ... ...
7 ... ... ...
8 ... ... ...
0 DISABLED
1 6 8, 16, 30, 59, 115 and 224 s 15 minutes
2 30 20, 40 s and 5 min. to the end 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 and 7 min 15 minutes
4 6 10, 20, 30, 60, 130 and 600 s 15 minutes
5 6 2, 4 y 8 min. to the end 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 and 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 minutes to the rest 15 minutes
10
10 3 minutes 30 minutes
11 7 2, 4, 8, 16, 32, 32 and 32 minutes 15 minutes
12 31 2, 4 and 6 minutes to the rest 15 minutes
13 6 8 s 15 minutes
14 ... ... ...
MAG
MAG
MAG
MAG
MAG
MAG
MAG
REC
REC
GREEN LED: ON
RED LED: TRIPPED BY FAULT
SCREENS /
SETUP
R
RESET button: It reinitiates the operation of the equipment by any event
that tripps it.evento. It indicates the equipment version.
YELLOW LED: Locked by reclosures (fix)
Betwen reclosures (blinking)
-
RST.C
, (
), initiates the partials counters.
NO
-
TRIP, (
), breaking element
(without trip coil)
MA
-
FREQ
, (
) frecuency (Hz)
50
-
LIM
,(
), range of values (Id / td)
1s, 3A
-
SEC. T
, (
),contacts 5-6 [NA/NC]
NO
Default values in
SETUP
TEST button: It makes a forced firing to verify the protection.
Button
FREQ
LIM
SEC.T
TRIP
Button
60 Hz
10 s, 30 A
RST.C
Mb
Pulsador
PROG
PsI
50 Hz
1 s, 3 A
St
MA
YES
NO
SETUP
SETTINGS
A long press in
activates the
SETUP
settings. In this operating
PROG
mode by pressing buttons
and it shows the submenus and the
PROG
setting values to modify . With
these
PROG
new setting values are
validated, the message
SAVE
is shown by display and exits setting
mode. In case of keypad inactive, it exits setting mode and the message
EXIT
is shown by display wihtout changes.
In
SEC.T
it defines the working mode of outputs contacts relay 5-6. By
default 5-6 is normally open (St )
In
TRIP
(Circuit Breaker), The value is used when the CB don’t need a
trip coil. The value is used when CB needs one.
(LOCKED SIGNAL)
(See graph)
(See graph)