67
Instruction Manual
COMPACT DC
6�- TECHNICAL FEATURES
AC Power supply
Rated voltage
110 ...230 V ~ ± 20%
Frequency
50/60Hz
Consumption
COMPACT DC 3G
COMPACT DC-S 3G
COMPACT DC 4I
COMPACT DC-S 4I
COMPACT DC SBT
COMPACT DC-S SBT
COMPACT DC 2
10...26 VA
12...27 VA
7...20 VA
11 ... 19 VA
Installation category
CAT III 300 V
Voltage measurement circuit of the LV monitor : BT : SBT and SBT-S ( COMPACT DC 2 model)
Voltage measurement margin
127/220 ... 230/400 V ~
± 20%
Frequency measurement margin
45 ... 65 Hz
Input impedance
800 k
Ω
Minimum measurement voltage (Vstart)
10 V ~
Maximum voltage input consumption
0.07 VA
Installation category
CAT III 600 V
Current measurement circuit of the LV monitor : BT : SBT and SBT-S (COMPACT DC 2 model)
Nominal current (In)
5 A
Current measurement margin
2 mA ... 10 A
Maximum current, impulse < 0�5 s
20*In
Minimum measurement current (Istart)
2 mA
Maximum current input consumption
0.02 VA
Installation category
CAT III 600 V
Measurement accuracy of the LV monitor : BT : SBT and SBT-S (COMPACT DC 2 model)
Voltage measurement
1%
Current measurement @ In
1%
Active energy measurement
Class B (1)
Reactive energy measurement
Class 2
PLC coupling circuit : PLC and PLC-S (COMPACT DC 2 model)
Rated voltage
Phase - Neutral
Phase-Phase
127 ... 230 V ± 20%
220 ... 400 V ± 20%
Frequency
45 ... 65 Hz
Modulation
OFDM (PRIME)
Band
CENELEC A
Coupling
COMPACT DC 3G/4I/SBT/2
COMPACT DC-S 3G/4I/SBT
Tx selective
Rx/Tx selective
3G modem (COMPACT DC/DC-S 3G model)
Brand
HUAWEI MU609
Type
Quad-band HSPA + HSPA/UMTS 850/900/1900/2100 MHz
Maximum output power
UMTS/3G (Power Class 3): 24 dBm
SIM card
miniSIM with double docking
Antenna
female SMA connector
Digital inputs (COMPACT DC/DC-S 4I and COMPACT DC 2 model)
Quantity
4
Type
Short-circuit (Vout max = 12.5 V
, Imax = 15 mA)
Insulation
10kV@1min