16
PV-Monitor-M
Instruction Manual
5.5.-
STEP 5
: CONFIGURATION OF THE RS-485 BUS
The
PV-Monitor-M
model communicates with the
TRH16
and with the
MET-485 sensor
via the
RS-485 bus.
The following must be configured for both devices to communicate:
A�- TRH16
Peripheral number:
2
Selector Position:
HI = 0, LOW=2
Transmission speed:
38400 bauds
Position of the dips:
Dip1: ON
(up)
, Dip2: OFF
(down)
B�- MET-485 sensor
The parameters of the probe have already been configured, so its installation is plug&play. You
only need to power the probe and connect the RS-485 bus.
Note:
Please refer to the instruction manuals if you have any doubts in relation to the configu
-
ration of the devices.
5.6.-
STEP 6
: CONFIGURATION OF THE INSTALLATION PARAMETERS
Access the
PV-Monitor-M
application and configure:
the parameters of the PV installation, see
the alarm parameters
,
see
“6�4�- CONFIGURATION OF THE ALARMS”�