40
RECmax-CVM
Instruction Manual
6�2�- AUTOMATIC RECLOSING
To configure the automatic reclosing parameters, press the
PROG
key for more than 3 seconds, while
the
Leakage current
or
Total no� of trips
screen is displayed�
RESET
RESET
RESET
RESET
RESET
RESET
mA
I n
REC
PROG
PROG
PROG
PROG
PROG
PROG
PROG > 3s
REC
N
Figure 33: Configuration: Automatic reclosing�
6�2�1�- SRD: EARTH LEAKAGE RECLOSING SEQUENCE
The reclosing parameters are configured on this screen after an earth leakage protection trip�
PROG
PROG
PROG
Press the
RESET
key to move between the different sequences available (
DI
)�
Each sequence determines the maximum no� of reclosing attempts (
NR
), the timer (
ST
) and the reset
time of the partial meter (
TR
shows the different sequences�
Table 20: Available sequences (SDR)�
SDR: Available sequences
DI
NR
ST
TR
DI 0
Automatic reclosing is disabled by earth leakage relay
DI 1
6
8, 16, 30, 59, 115 and 224s
15 min�
DI 2
30
20s, 40s and 5 min� the rest
15 min�
DI 3
8
30s, 1, 2, 3, 4, 5, 6, and 7 min�
15 min�
DI 4
6
10, 20, 30, 60, 130 and 600s�
15 min�
DI 5
6
2, 4 and 8 min� the rest
15 min�