21
Instruction Manual
RECmax-CVM
4�5�- LED INDICATORS
The device has 2 indicator LEDs,
�
LEDs
Figure 13: RECmax-CVM LED indicators�
Table 7: Description of the LEDs: Normal operating status�
Normal operating status
LED
Description
Green
Permanent:
Powered device�
Flashing:
Indicates that the value of the power supply > 265 V�
Red
Off
Table 8: Description of the LEDs: Trip status�
Trip status
LED
Description
Green
Off
Red
Flashing:
The device is waiting for the time needed for an automatic reclosing attempt�
Permanent:
Automatic reclosing is not possible�
The flashing or simultaneous switching on of the
Red
and
Green
LEDs indicates
that the device is not working correctly, either because of an intrinsic problem
in the device or due to improper installation�
Note:
One of the most frequent causes of improper installation is that the earth leakage transformer
has not been connected. In that case the
Red
LED comes on and the
Green