41
Instruction Manual
RECmax-CVM
Table 20 (Cont�): Available sequences (SDR)�
SDR: Available sequences
DI
NR
ST
TR
DI 6
7
30s, 1, 2, 3, 4, 8 and 16 min�
30 min�
DI 7
10
1 min�
30 min�
DI 8
10
90 s�
30 min�
DI 9
8
2, 4 and 6 min� the rest
15 min�
DI 10
10
3 min�
30 min�
DI 11
7
2, 4, 8, 16 and 32 min� the rest
15 min�
DI 12
31
2, 4 and 6 min� the rest
60 min�
DI 13
3
2, 4 and 8 min�
15 min�
DI 14
Free space for personalising the customer�
Press the
PROG
key to save the selected sequence and exit the setup menu; when exiting, the screen
in
is displayed for a few seconds�
If you do not press any key for 10 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made�
Default value: DI 10
6�2�2�- SRM: CIRCUIT BREAKER RECLOSING SEQUENCE
The reclosing parameters are configured on this screen after a circuit breaker trip�
PROG
PROG
PROG
Press the
RESET
key to move between the different sequences available (
MA
)�
Each sequence determines the maximum no� of reclosing attempts (
NR
), the timer (
ST
) and the reset
time of the partial meter (
TR
shows the different sequences�
Table 21: Available sequences (SRM)�
SRM: Available sequences
MA
NR
ST
TR
MA 0
Automatic reclosing is disabled by circuit breaker
MA 1
2
1 min�
30 min�
MA 2
2
1 min�
60 min�
MA 3
2
90 s
30 min�
MA 4
2
90 s
60 min�
MA 5
2
3 min�
30 min�
MA 6
2
30 s
30 min�
MA 7
6
30 s
30 min�
MA 8
Free space for personalising the customer�