Table 38:Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
Address
Voltage primary
2710 - 2711
Voltage secondary
2712
Current primary
2713
Current secondary
2714
7�3�13�2� Number of quadrants
The
Function 0x04
is implemented for these variables�
Table 39:Modbus memory map: Number of quadrants
Number of quadrants
Configuration variable
Address
Valid data margin
Number of quadrants
2B24
0:
4 quadrants
1:
2 quadrants
7�3�13�3� Maximum demand
The
Functions 0x04
and
0x10
are implemented for this variable�
Table 40:Modbus memory map: Maximum demand
Maximum demand
Configuration variable
Address
Valid data margin
Default value
Integration period
274C
1 - 60
minutes
15
Type of integration
274D
0:
sliding
1:
2 fixed
0
7�3�13�4� Configuration of the THD
The
Functions 0x04
and
0x10
are implemented for this variable�
In this parameter, select the type of calculation of the THD�
Table 41:Modbus memory map: THD Configuration
THD Configuration
Configuration variable
Address
Valid data margin
Default value
THD calculation
2774
0:
RMS
1:
fundamental
0
7�3�13�5� Programming the Digital Output
The
Functions
0x04
and
0x10
implemented for this variable�
You can configure the operation of the Digital Output
with these parameters (terminals 7 and 8 in
)