17
Instruction Manual
RECmax Lpd
4�6�-
INPUTS
The
RECmax Lpd
has one key:
EXT
input
(terminals 12 and 13 in
) enables the remote control of the main switch, trip
or reset of the switch depending on its status.
The input is activated when terminals 12-13 are short circuited with an external contact (volt-
age-free), for example a button.
EXT
input acts as an edge-triggered bistable, T-type input, i.e.,
the status of the main switch changes on each pulse, if the switch is open it closes, if it is closed
it opens.
Table 9: Inputs�
Inputs
Type
Activation mode
EXT
Voltage-free
200 ms pulses
4�7�- OUTPUTS
The
RECmax Lpd
has three outputs:
TRIP locking alarm
) indicates that the device is locked, i.e. that
it cannot be automatically reclosed and needs a manual or external reset to recover its normal
operation.
Table 10: TRIP locking alarm�
Automatic
reclosing
TRIP locking alarm
Contact 9 - 10
Open
X
Closed
Note:
The
TRIP locking alarm
has the
Positive safety
Configuration; loss of power is treated
as an alarm. This type of operation can be configured, see
“6.2.4.- POLT: CONFIGURATION OF THE
If configured
without positive safety
and the device loses power, the device
may be locked and the
TRIP
output won't be activated.
AUX fault alarm
(terminals 14 and 15 in
) indicates whether there is any power or not.
Table 11: AUX fault alarm�
Power supply
AUX fault alarm
Contact 14 - 15
Closed
X
Open
Note:
The contact is controlled by the internal microprocessor and therefore, if there is a fault