27
Instruction Manual
RECmax Lpd
6�2�- AUTOMATIC RECLOSING
To configure the automatic reclosing parameters, press the
PROG
key for more than 3 seconds, while
the
Leakage current
or
Total no� of trips
screen is displayed.
RESET
RESET
RESET
RESET
RESET
RESET
mA
I n
REC
PROG
PROG
PROG
PROG
PROG
PROG
PROG > 3s
REC
N
Figure 17: Configuration: Automatic reclosing�
6�2�1�- SRD: EARTH LEAKAGE RECLOSING SEQUENCE
The reclosing parameters are configured on this screen after an earth leakage protection trip.
PROG
PROG
PROG
Press the
RESET
key to move between the different sequences available (
DI
).
Each sequence determines the maximum no. of reclosing attempts (
NR
), the timer (
ST
) and the reset
time of the partial meter (
TR
).
shows the different sequences.
Table 20: Available sequences (SDR)�
SDR: Available sequences
DI
NR
ST
TR
DI 0
Automatic reclosing is disabled by earth leakage relay
DI 1
6
8, 16, 30, 59, 115 and 224s
15 min.
DI 2
30
20s, 40s and 5 min. the rest
15 min.
DI 3
8
30s, 1, 2, 3, 4, 5, 6, and 7 min.
15 min.
DI 4
6
10, 20, 30, 60, 130 and 600s.
15 min.
DI 5
6
2, 4 and 8 min. the rest
15 min.
DI 6
7
30s, 1, 2, 3, 4, 8 and 16 min.
30 min.