28
RECmax Lpd
Instruction Manual
Table 20 (Cont�): Available sequences (SDR)�
SDR: Available sequences
DI
NR
ST
TR
DI 7
10
1 min.
30 min.
DI 8
10
90 s.
30 min.
DI 9
8
2, 4 and 6 min. the rest
15 min.
DI 10
10
3 min.
30 min.
DI 11
7
2, 4, 8, 16 and 32 min. the rest
15 min.
DI 12
31
2, 4 and 6 min. the rest
60 min.
DI 13
3
2, 4 and 8 min.
15 min.
DI 14
Free space for personalising the customer.
Press the
PROG
key to save the selected sequence and exit the setup menu; when exiting, the screen
in
is displayed for a few seconds.
If you do not press any key for 5 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made.
Default value:
DI 10
6�2�2�- SRM: CIRCUIT BREAKER RECLOSING SEQUENCE
The reclosing parameters are configured on this screen after a circuit breaker trip.
PROG
PROG
PROG
Press the
RESET
key to move between the different sequences available (
MA
).
Each sequence determines the maximum no. of reclosing attempts (
NR
), the timer (
ST
) and the reset
time of the partial meter (
TR
).
shows the different sequences.
Table 21: Available sequences (SRM)�
SRM: Available sequences
MA
NR
ST
TR
MA 0
Automatic reclosing is disabled by circuit breaker
MA 1
2
1 min.
30 min.
MA 2
2
1 min.
60 min.
MA 3
2
90 s
30 min.
MA 4
2
90 s
60 min.
MA 5
2
3 min.
30 min.
MA 6
2
30 s
30 min.
MA 7
6
30 s
30 min.
MA 8
Free space for personalising the customer.