22
RGU-10 MT
Instruction Manual
4�7�- TROUBLESHOOTING OR REASONS FOR TRIPPING
In the event of an earth leakage current trip due to a fault, test or error of the earth leakage trans-
former.
1�-
Look at the red display for the cause of the trip.
2�-
The device starts a timer based on the sequence selected in the event of a trip.
3�-
The device reconnects by applying voltage to the motor (ON).
4�7�1�- POOR TOROID CONNECTION ALARM
After a certain time the device will carry out a test to detect the presence of the sensor or associated
earth leakage transformer.
Also the “
ERRt”
error message will permanently appear on the
RGU-10 MT
display.
A short-circuit in the transformer secondary will also be detected as an error.
When this error is detected, the correct connection with the earth leakage transformer has to be en-
sured and a
RESET
made to re-establish proper working. If the transformer is detected again, normal
status is returned and the error message disappears.
Figure 16: Alarm by poor toroid connection�
4�7�2�- TRIP ON DIFFERENTIAL FAILURE
When the device trips due to a fault current, the red LED is on continuously, the yellow LED flashes, and
the LCD is backlit red. The display shows the current of the last cycle that tripped the relay, and shows
a “
DIF
” message.
Figure 17: Trip on differential failure�
Summary of Contents for RGU-10 MT
Page 1: ...INSTRUCTION MANUAL Electronic earth leakage protection relay RGU 10 MT Serie M98228501 03 21A...
Page 2: ...2 RGU 10 MT Instruction Manual...
Page 38: ...38 RGU 10 MT Instruction Manual 12 CE CERTIFICATE...
Page 39: ...39 Instruction Manual RGU 10 MT...
Page 40: ...40 RGU 10 MT Instruction Manual...