3�2�- INSTALLATION
While the device is connected, the terminals, opening the cover or removing ele-
ments can expose parts that are hazardous to the touch. The device must not be
used until the installation process is complete.
The device is installed on a DIN rail or on a panel (drilled panel 67
+1
x 67
+1
mm, according to DIN 43 700
using accessory). All connections must remain inside the electrical board.
The device has to be connected to a power circuit protected with gL fuses (IEC 60269) or type M fuses
between 0.5 and 2 A. The power circuit, in turn, must be fitted with a circuit breaker or equivalent
device to disconnect the device from the mains supply.
Twisted cable should be used if connecting the earth leakage transformer over long distances.
3�2�1�- INSTALLATION OF DEVICE IN PANEL
A 72x72 mm front adapter accessory is used to install the device on a panel. All connections must re-
main inside the electrical board.
The front adapter accessory has a base, a frame two tabs and three screws,
.
Figure 1:Adapter accessory�
The steps to follow to perform the installation of the adapter accessory are:
1�-
The base is mounted on top of the device.
2�-
The device is attached by screwing the holes in the device on the upper right corner and lower left
corner on the front of device.
3�-
The front frame is attached to cover the mounting points.
4�-
Three green pressure tabs on the side runners of the base are attached.
5�-
The device is mounted in the hole in the panel with the adapter.
6�-
The tabs run towards the panel to obtain the mounting pressure.