27
Instruction Manual
RGU-10, RGU-10C
4�7�3�- FAULT TRIP
When the device is tripped by a current fault, the red and yellow LED comes on and the backlit
LCD is red. There remains the display of the current of the last cycle that the relay has tripped.
To reconnect press
RESET
to return to the initial status.
Figure 19: Fault trip�
4�7�4�- REMOTE TRIP
When a trip is forced (input terminals
1-2
, by applying
230 V
) the device is tripped and disabled
and an “
EXT
” message is shown on the display in red and also the LED is on. It has to remain
permanently in this situation until the change in status no longer exists. It is not possible to
manually reset or reset using communications.
Figure 20: Remote trip�
When it is remotely reset (input terminals
1-2
, removing the
230 Vac
) the equipment is recon-
nected with the display backlit in green, LED
ON
in green as in normal status.
For the
RGU-10C
, a remote trip/reset can also be made via RS-485 communications. The de-
vice remains tripped showing this incidence on the display with a “
REM
” message in red with
also the LED
ON
. It has to remain permanently in this situation until the change in status no
longer exists.
Figure 21: Remote trip via RS-485�
It is reset when the remote reset is carried out using RS-485 communications, applying 230
Vac between the remote
1-2
input terminals or by pressing the
RESET
button. The device is
reconnected with the display backlit in green, LED
ON
in green as in normal status.