40
RGU-100B
Instruction Manual
Table 20 (Continued): Modbus Memory Map: Relay curve or delay table�
Relay curve or delay table�
Parameter
Format
Address
Value
Value 9
Unit [16]
0x04
100C
1000
ms -
0
(4)
Value 10
Unit [16]
0x04
100D
3000
ms -
0
(4)
Value 11
Unit [16]
0x04
100E
5000
ms -
0
(4)
Value 12
Unit [16]
0x04
100F
10000
ms -
0
(4)
Value 13
Unit [16]
0x04
1010
0
(3)
Value 14
Unit [16]
0x04
1011
0
(3)
Value 15
Unit [16]
0x04
1012
0
(3)
Value 16
Unit [16]
0x04
1013
0
(3)
(4)
0:
Indicates that the value is not available.
Table 21: Modbus Memory Map: Trip current table�
Trip current
Parameter
Format
Function
Address
Value
Value 1
Unit [16]
0x04
1014
30
mA -
0
(5)
Value 2
Unit [16]
0x04
1015
100
mA -
0
(5)
Value 3
Unit [16]
0x04
1016
300
mA -
0
(5)
Value 4
Unit [16]
0x04
1017
500
mA -
0
(5)
Value 5
Unit [16]
0x04
1018
1000
mA -
0
(5)
Value 6
Unit [16]
0x04
1019
3000
mA -
0
(5)
Value 7
Unit [16]
0x04
101A
0
(4)
Value 8
Unit [16]
0x04
101B
0
(4)
Value 9
Unit [16]
0x04
101C
0
(4)
Value 10
Unit [16]
0x04
101D
0
(5)
Value 11
Unit [16]
0x04
101E
0
(5)
Value 12
Unit [16]
0x04
101F
0
(5)
Value 13
Unit [16]
0x04
1020
0
(5)
Value 14
Unit [16]
0x04
1021
0
(5)
Value 15
Unit [16]
0x04
1022
0
(5)
Value 16
Unit [16]
0x04
1023
0
(5)
(5)
0:
Indicates that the value is not available.
7�3�5�2�- RS-485 communications
Table 22: Modbus Memory Map: SR-485 Communications�
RS-485 Communications
Configuration variable
Format
Address
Valid data range
Default value
Peripheral number
Unit [16]
36B0
1... 247
1
Baud rate
Unit [32]
36B1 - 36B2
4800, 9600, 19200, 38400,
57600, 115200
9600
Data format
Unit [16]
36B3
0:
8N1,
1:
8E1,
2:
801
3:
8N2,
4:
8E2,
5:
802
0
Summary of Contents for RGU-100B
Page 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 100B M256B01 03 20A...
Page 2: ...2 RGU 100B Instruction Manual...
Page 47: ...47 Instruction Manual RGU 100B 11 CE CERTIFICATE...
Page 48: ...48 RGU 100B Instruction Manual...
Page 49: ...49 Instruction Manual RGU 100B...
Page 53: ...53 Instruction Manual RGU 100B...